2020-03-03 12:34:15FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR WORK IS LOW. PROVIDE A SIGNED CONTRACT FOR
 THE WORK. SEVERAL NOTES INCLUDE MATERIALS SUPPLIED BY
 OWNER THESE ITEMS NEED TO BE INCLUDED WITH THE PERMIT.
  
 2) RISER DIAGRAM DOES NOT SHOW GENERATOR TAP BOX SHOWN
 ON OUTSIDE OF BUILDING
  
 3) THERE SEEMS TO BE AREAS WHERE GFCI RPOTECTION IS
 REQUIRED THAT IS LACKING (KITCHEN, WITHIN, 6' OF A
 SINK) PLEASE INDICATE ON THE PLANS GFCI PROTECTION.
  
 3) PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 4) CIRCUIT "L" 40 TO BE GFCI PROTECTED PER 422.23
 422.23 TIRE INFLATION AND AUTOMOTIVE VACUUM MACHINES
 TIRE INFLATION MACHINES AND AUTOMOTIVE VACUUM MACHINES
 PROVIDED
 FOR PUBLIC USE SHALL BE PROTECTED BY A GROUND-FAULT
 CIRCUIT
 INTERRUPTER.
  