| Plan Review Notes For Permit 20010941 |
| Permit Number |
20010941 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-03-03 12:34:15 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE FOR WORK IS LOW. PROVIDE A SIGNED CONTRACT FOR | | | THE WORK. SEVERAL NOTES INCLUDE MATERIALS SUPPLIED BY | | | OWNER THESE ITEMS NEED TO BE INCLUDED WITH THE PERMIT. | | | | | | 2) RISER DIAGRAM DOES NOT SHOW GENERATOR TAP BOX SHOWN | | | ON OUTSIDE OF BUILDING | | | | | | 3) THERE SEEMS TO BE AREAS WHERE GFCI RPOTECTION IS | | | REQUIRED THAT IS LACKING (KITCHEN, WITHIN, 6' OF A | | | SINK) PLEASE INDICATE ON THE PLANS GFCI PROTECTION. | | | | | | 3) PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT | | | CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. | | | NEC 110.10 | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | 4) CIRCUIT "L" 40 TO BE GFCI PROTECTED PER 422.23 | | | 422.23 TIRE INFLATION AND AUTOMOTIVE VACUUM MACHINES | | | TIRE INFLATION MACHINES AND AUTOMOTIVE VACUUM MACHINES | | | PROVIDED | | | FOR PUBLIC USE SHALL BE PROTECTED BY A GROUND-FAULT | | | CIRCUIT | | | INTERRUPTER. | | | |
|