Plan Review Notes
Plan Review Notes For Permit 20010941
Permit Number 20010941
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-24 14:20:192017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010941
 ADD: 5300 45TH ST.
 CONT: TBD / TO BE DETERMINED
 TEL: 856-6655 / CONTACT: NEYITA LEIVA
 E-MAIL: NEYITA@/PS01.NET
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 24TH/ 2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE ADDRESS AS 5300
 45TH ST. AND WITHIN THE TITLEBLOCK. WHEN VIEWING THIS
 ADDRESS ON GOOGLE MAPS THERE APPEARS TO BE 4 TENANTS
 A-D. THE DEMOLITION PLAN IT WOULD APPEAR THE EXISTING
 TIRE SHOP IS GOING TO REMAIN. HOW WILL THE TENANT
 ADDRESSES BE IDENTIFIED?
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) THE DEMOLITION SHEET A1.7 SHOWS INTERIOR TENANT
 SEPARATION WALLS BEING REMOVED BUT THE NOTE TAG # 22
 INDICATES THIS IS AN EXISTING GREASE TRAP TO REMAIN.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED, IT
 APPEARS THERE IS A TYPO. AN EXISTING GREASE TRAP IS
 NOTED ON THE PLANS BUT NOT SHOWN.
  
 3A) SHEET A0.1 CODE COMPLIANCE INFORMATION SHEET AND
 SHEET A1.5 THE EGRESS PLAN BOTH SHOW MERCANTILE AND THE
 SALES AREAS WITHIN THE TENANT SPACE TAKING THE OCCUPANT
 LOAD FACTOR @ 30 SQ. FEET PER OCCUPANT.
 PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2. THE
 MERCANTILE OCCUPANT LOAD FACTOR IS TAKEN AT 60 SQ. FT.
 / OCCUPANT THIS WAS CHANGED IN THE 2017 FBC-B CODE.
  
 3B) WITH THE REVISED OCCUPANT LOAD OF 50 THE TENANT
 SPACE WOULD STILL REQUIRE 2 EXITS FOR THE PUBLIC, NOT
 THROUGH THE STOREROOM.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 IS THE BACK EGRESS DOOR HAVE A LANDING THAT IS AT GRADE
 AND LEAD TO THE PUBLIC WAY? SEE THE 2017 FBC-B 1028.5
 ACCESS TO THE PUBLIC WAY.
  
 4A) SHEET A1.3 THE ARCHITECTURAL SITE PLAN SHOWS 2
 ACCESSIBLE PARKING SPACES 18 & 19 BUT THE PLANS DO NOT
 SHOW COMPLIANCE WITH THE CITY STANDARD OF DOUBLE LINED
 STRIPES AND COMPLIANCE WITH THE CITY OF WEST PALM BEACH
 ACCESSIBLE PARKING STANDARD. AN ACCESSIBLE PARKING
 SPACE AND ACCESS AISLE, PLEASE SEE THE 2017
 FBC-ACCESSIBILITY CODE 502.3.3 MARKING. ACCESS AISLES
 SHALL BE MARKED SO AS TO DISCOURAGE PARKING IN THEM.
 THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
  
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA
 LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF
 ACCESS AISLES.
 THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDES A DOUBLE LINED DIMENSIONED PARKING
 STALL DETAIL.
  
 4B) SHEET A1.3 THE ARCHITECTURAL SITE PLAN SHOWS THE
 ACCESS AISLE BETWEEN THE ACCESSIBLE PARKING SPACES BUT
 THE PLANS DO NOT INDICATE HOW THE TRANSITION (DROPPED
 CURB/ CURB CUT) IS MADE BETWEEN THE SIDEWALK AND ACCESS
 AISLE. 2017 FBC-ACCESSIBILITY CODE SECTION 406 CURB
 RAMPS. THE ACCESSIBILITY DETAIL SHEET DOES NOT PROVIDE
 CODE COMPLIANCE IN ANY OF THE DETAILS, NEITHER.
  
 4C) SHEET A1.3 THE ARCHITECTURAL SITE PLAN SHOWS 2
 PARKING SPACES IN THE FRONT OF THE BUILDING WITH AN
 ASTERISK SIGN AND 6 BEHIND THE BUILDING IN BOTH CASES
 KEYNOTE # 4 IS SHOWN AND THE COMMENT PARKING REFER TO
 THE CIVIL SHEETS. THEY ARE NOT PART OF THIS SET OF
 PLANS. ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
  
 4D) IN THE SITE PLAN THE CANOPY AND GAS PUMPS ARE
 SHOWN, ARE THE EXISTING PUMPS AND CANOPY GOING TO BE
 REUSED, OR ARE THEY BEING DEMOLISHED AND NEW PUMPS AND
 CANOPY GOING TO BE SUBMITTED UNDER SEPARATE PERMITS
 WITH ASSOCIATED REVIEW AND FEES. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) THE EGRESS SHEET A1.5 SHOWS A NEW COOLER VAULT AND
 BEER CAVE. THEIR COMBINED / AGGREGATE FLOOR AREA IS 458
 SQ. FT. EXTERIOR OF COOLER AND 423 SQ. FT. ON THE
 INTERIOR SIDE OF THE NEW COOLER AND BEER CAVE. PLEASE
 BE AWARE OF SECTION 2603.4.1.3. THAT LIMITS THE
 AGGREGATE AREA OF WALK IN COOLERS TO 400 SQ. FT. IN
 NON-SPRINKLERED BUILDINGS. PLEASE BE AWARE THERE ARE
 OTHER CRITERIA THAT HAS TO BE PROVIDED AS WELL. A
 SEPARATE PERMIT REVIEW AND ASSOCIATED FEES WILL BE
 REQUIRED.
  
 6) SHEET A2.1 THE ENLARGED RESTROOM DETAIL # 1 SHOWS
 THE HIGH/ LOW DRINKING FOUNTAINS BUT THERE IS NO
 ELEVATION VIEW TO INDICATE THE TYPE OF DRINKING
 FOUNTAIN AND COMPLIANCE WITH PROTRUDING OBJECTS AS
 FOUND ON SHEET A1.2. THE ISSUE, MAYBE WITH THE HIGH
 DRINKING FOUNTAIN IS A SKIRT MAYBE NEED TO BE ADDED TO
 THE BOTTOM OF THE ENCLOSURE FOR COMPLIANCE WITH
 PROTRUDING OBJECTS FROM THE WALL AND COMPLIANCE WITH
 THE 2017 FBC-ACCESSIBILITY CODE SECTION 307.2
 PROTRUSION LIMITS. OBJECTS WITH THE LEADING EDGE MORE
 THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE
 FINISH FLOOR OR GROUND SHALL PROTRUDE 4 INCHES MAXIMUM
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 7) SHEET A2.4, M1.1 & S102 ROOF PLANS ALL SHOW NEW ROOF
 TOP EQUIPMENT. SHEET M1.1 SHOWS THE BEER CAVE BACKSTOCK
 CONDENSER WITHIN 10 FEET OF THE ROOF EDGE.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B:
 2017 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL BE
 PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH
 OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES IN DIAMETER.
 THE GUARD SHALL EXTEND NOT LESS THAN 30 INCHES BEYOND
 EACH END OF SUCH APPLIANCE, EQUIPMENT, FAN OR
 COMPONENT.
  
 8) THE PLANS ELEVATIONS WILL NEED TO SHOW HOW
 COMPLIANCE WITH SECTION 2017 FBC-M 306.5. EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. WHERE
 EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE LOCATED ON
 AN ELEVATED STRUCTURE OR ROOF OF A BUILDING SUCH AS
 PERSONNEL WILL HAVE TO CLIMB HIGHER THAN 16 FEET ABOVE
 GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN
 INTERIOR OR EXTERIOR MEANS OF EGRESS SHALL BE PROVIDED.
  
 9) SHEETS A2.4 & M1.1 WILL NEED TO SHOW COMPLIANCE FOR
 ROOF TOP A/C CONDENSER STANDS WITH COMPLIANCE WHERE
 ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON RAISED
 EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE HEIGHT
 IN ACCORDANCE WITH TABLE 1510.10 OF THE 2017 FBC-B.
  
 10) ROOF TOP CONDENSING STANDS WILL NEED TO BE REVIEWED
 BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 11) SHEET S201 SHOWS WELDED CONNECTIONS TO THE BAR
 JOIST, STIFFENERS, ADDITIONAL STEEL FRAMING AROUND NEW
 ROOF TOP OPENINGS. WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 11A) 2017 FBC-B 2204.1 WELDING
 11B) 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 12) NO ACTION REQUIRED. SHEET S001 PROVIDES THE WIND
 DESIGN CRITERIA AND ASSOCIATED PRESSURES, WHICH ARE
 CORRECT.
  
 13) COMPONENTS & CLADDING . 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (G) PRE-ENGINEERED A/C STANDS
  
 14) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 17) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  