2020-02-25 08:47:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 PLUMBING COMMENTS: DENIED
  
 1.PER FBC PL 912.1, KITCHEN SINK SHALL NOT CONNECT TO
 THE WET VENTED BATHROOM GROUP. CONNECT SINK FIXTURE
 DRAIN DOWNSTREAM OF THE LAVATORY OR PROVIDE INDIVIDUAL
 VENT FOR THE WATER CLOSET.
 2.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR THE TANKLESS WATER HEATER AND DELETE
 THE WORDS "OR EQUIVALENT" FROM THE DESCRIPTION.
  
 3.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 3 AND 6 PROVIDE DETAILS INDICATING THE
 FOLLOWING:
  
 A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
 C.SHOW CLEAR FLOOR SPACE FOR SINK. THE CLEAR FLOOR OR
 GROUND SPACE SHALL BE 30 INCHES (760 MM) MINIMUM BY 48
 INCHES (1220 MM) MINIMUM AND COMPLY WITH FBC ACC
 SECTION 305.
  
 4. PER WPB FBC 107.2.1, COMPLETE THE ENERGY
 CALCULATIONS FORM AND INCLUDE THE REPORT ON THE WATER
 HEATING SYSTEMS AND THE PIPING SYSTEMS.
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  