Plan Review Notes
Plan Review Notes For Permit 20010892
Permit Number 20010892
Review Stop E
Sequence Number 1
Notes
Date Text
2020-02-14 06:18:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL DESIGNS OVER 240VOLTS OR $125,000 MUST BE
 DESIGNED AND SIGNED SEALED BY A DESIGN PROFESSIONAL.
 ELECTRONICALLY SUBMITTED DOCUMENTS MUST BE DIGIALLY
 SIGNED.
  
 471.003?QUALIFICATIONS FOR PRACTICE; EXEMPTIONS.
  
 (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR
 MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE
 DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY,
 WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED
 UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR
 UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY
 CONSTRUCTION PROJECT WHICH:
  
 1. REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
 2. REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM.
  
  
  
 2.PROVIDE NOTE ON PLAN STATING LOW VOLTAGE SHOWN WILL
 REQUIRE A SEPARATE LOW VOLTAGE PERMIT. FBC 105.1
  
 3. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
  
 4.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 5.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
  
 6.CONDUCTOR SIZES FOR 30KVA TRANSFORMER SHOWN ON PLANS
 ARE INCORRECT. MUST BE #6 CU FOR PRIMARY AND #1/0
 SECONDARY. PROVIDE CORRECTION. NEC 110.14(C)(1)(A)(2),
 215.2(A)(1)(A), 310.15(B)(16) 240.21(C)
  
 7.PLAN SHOWS HIGH AND LOW VOLTAGE CONDUCTORS IN SAME
 CONDUIT FROM LCP TO FOUNTAIN. CANNOT MIX HIGH AND LOW
 VOLTAGE. PROVIDE CORRECTION. NEC 725.136B
  
 8.LCP IS FED WITH #12 WIRE BUT HAS A BRANCH CIRCUIT OF
 #8'S??? PROVIDE CORRECTION/CLARIFICATION. FBC 1`07.2.1
  
 9.NO PANEL SCHEDULE SHOWN FOR LCP. PROVIDE CORRECTION.
 FBC 107.2.1
  
 10. PLAN SHOWS "LCP TYPICAL OF 2" BUT ONLY SHOWS ONE
 LCP PANEL. PROVIDE CORRECTION/CLARIFICATION FBC 107.2.1
  
 11. 30KVA TRANSFORMER MUST HAVE GROUNDING ELECTRODE
 CONDUCTOR FROM A GROUNDING ELECTRODE SPECIFIED IN
 250.30A4 (1) OR (2) WHEN AVAILABLE. IF NOT AVAILABLE
 THEN ANOTHER SUPPLEMENTAL ELECTRODE WILL BE REQUIRED
 FOR TRANSFORMER. THE ONE GROUND ROD SHOWN DOES NOT
 SUFFICE. NEC 250.53A2
  
 12. PROVIDE CUT SHEETS OF ALL MATERIALS AND EQUIPMENT
 FOR PRODUCT APPROVAL. NEC 90.7, 110.2, 110.3B FBC
 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  