2020-03-25 13:27:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20010876 7000 OKEECHOBEE BLVD
  
 2ND REVIEW
 PLUMBING COMMENTS: APPROVED W/PROVISO
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 I.PLUMBING PROVISO
 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL MANUFACTURER?S SPECIFICATION
 AND INSTALLATION GUIDE FOR ALL SPECIALTY EQUIPMENT
 FURNISHED BY OWNER/VENDORS REQUIRING PLUMBING WATER
 AND/OR WASTE CONNECTIONS. DOCUMENT SHALL BE SUBMITTED,
 APPROVED AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED
 AT YOUR OWN RISK.
 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, A PLAN
 REVISION SHALL BE SUBMITTED OF A RECORD DRAWING.
 DOCUMENT SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR
 TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK.
 3. RE: PLAN SHEET P-501 AND P-011; WATER HEATER DETAIL
 AND TEMPERED WATER; TEMPERED WATER SHALL BE DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3 PER FBC PL
 416.5. DEVICE IS POINT OF USE AND ONE EACH SHALL BE
 PROVIDED AT EACH FIXTURE, NOT AT THE WATER HEATER.
 4. PER FBC PL 608.3, PROVIDE BACKFLOW PREVENTERS AT ALL
 POTABLE COLD AND FILTERED WATER CONNECTIONS TO THE
 FOLLOWING ITEMS: ICE MACHINES, COFFEE/EXPRESSO MAKERS,
 CARBONATED DRINK DISPENSERS, SANITIZERS, WATER PUMPS,
 FILTERS, SOFTENERS, TANKS AND OTHER DEVICES THAT HANDLE
 OR TREAT POTABLE AND/OR FILTERED WATER.
 DISCHARGE OF DRAINS FROM FORE MENTIONED EQUIPMENT AND
 BACKFLOW PREVENTERS SHALL DISCHARGE TO THE APPROPRIATE
 TRAPPED AND VENTED OPEN RECEPTACLE THROUGH AN AIR GAP
 IN ACCORDANCE WITH FBC PL 608.13.1
 5. PROVIDE TRAP SEAL PROTECTION FOR ALL FLOOR DRAINS
 PER FBC PL 1002.4.1.
 II. PLUMBING PROVISO: THE FOLLOWING NOTES ARE A
 CLARIFICATION OF FBC ACC REQUIREMENTS AND SHALL PREVAIL
 IN EVENT CONFLICTING INFORMATION PROVIDED ON THE PLAN;
 SEE PLAN SHEETS I-401 AND I-40101
 A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C. TURNING SPACE SHALL COMPLY WITH FBC ACC 304.3.1 OR
 304.3.2.
 D. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 E. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 F. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 G. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 H. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 I. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  