| 2020-03-25 13:27:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20010876 7000 OKEECHOBEE BLVD |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: APPROVED W/PROVISO |
| | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| | INSPECTOR'S APPROVAL |
| | I.PLUMBING PROVISO |
| | 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE |
| | AS A DEFERRED SUBMITTAL MANUFACTURER?S SPECIFICATION |
| | AND INSTALLATION GUIDE FOR ALL SPECIALTY EQUIPMENT |
| | FURNISHED BY OWNER/VENDORS REQUIRING PLUMBING WATER |
| | AND/OR WASTE CONNECTIONS. DOCUMENT SHALL BE SUBMITTED, |
| | APPROVED AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED |
| | AT YOUR OWN RISK. |
| | 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, A PLAN |
| | REVISION SHALL BE SUBMITTED OF A RECORD DRAWING. |
| | DOCUMENT SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR |
| | TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK. |
| | 3. RE: PLAN SHEET P-501 AND P-011; WATER HEATER DETAIL |
| | AND TEMPERED WATER; TEMPERED WATER SHALL BE DELIVERED |
| | FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN |
| | PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS, |
| | PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED |
| | THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070 OR CSA B125.3 PER FBC PL |
| | 416.5. DEVICE IS POINT OF USE AND ONE EACH SHALL BE |
| | PROVIDED AT EACH FIXTURE, NOT AT THE WATER HEATER. |
| | 4. PER FBC PL 608.3, PROVIDE BACKFLOW PREVENTERS AT ALL |
| | POTABLE COLD AND FILTERED WATER CONNECTIONS TO THE |
| | FOLLOWING ITEMS: ICE MACHINES, COFFEE/EXPRESSO MAKERS, |
| | CARBONATED DRINK DISPENSERS, SANITIZERS, WATER PUMPS, |
| | FILTERS, SOFTENERS, TANKS AND OTHER DEVICES THAT HANDLE |
| | OR TREAT POTABLE AND/OR FILTERED WATER. |
| | DISCHARGE OF DRAINS FROM FORE MENTIONED EQUIPMENT AND |
| | BACKFLOW PREVENTERS SHALL DISCHARGE TO THE APPROPRIATE |
| | TRAPPED AND VENTED OPEN RECEPTACLE THROUGH AN AIR GAP |
| | IN ACCORDANCE WITH FBC PL 608.13.1 |
| | 5. PROVIDE TRAP SEAL PROTECTION FOR ALL FLOOR DRAINS |
| | PER FBC PL 1002.4.1. |
| | II. PLUMBING PROVISO: THE FOLLOWING NOTES ARE A |
| | CLARIFICATION OF FBC ACC REQUIREMENTS AND SHALL PREVAIL |
| | IN EVENT CONFLICTING INFORMATION PROVIDED ON THE PLAN; |
| | SEE PLAN SHEETS I-401 AND I-40101 |
| | A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| | ACC 604.2 |
| | B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL PER FBC ACC 604.3.1 |
| | C. TURNING SPACE SHALL COMPLY WITH FBC ACC 304.3.1 OR |
| | 304.3.2. |
| | D. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL PER FBC ACC 604.5.1 |
| | E. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | F. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET PER FBC ACC 604.6 |
| | G. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| | ACC 604.8. |
| | H. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE |
| | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS |
| | REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | I. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2 |
| | |
| | |