Plan Review Notes
Plan Review Notes For Permit 20010876
Permit Number 20010876
Review Stop M
Sequence Number 2
Notes
Date Text
2020-03-25 09:07:532ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20010876
 3/25/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M001, M002, M101, & M601: AS PREVIOUSLY NOTED
 IN THE 1ST REVIEW, THE RTU'S FOR STARBUCKS WERE
 INSTALLED UNDER PERMIT #19010177. PLEASE CORRECT THE
 REFERENCES TO PERMIT #19081537 - SECTION 107.2.1 WPB.
  
 2) UNDER PERMIT #19090177, THE ENGINEER OF RECORD TODD
 W. CAREY P.E DID NOT PROVIDE EITHER ENERGY OR AC
 CALCULATIONS ACCORDING TO WHAT HE SAID WAS FROM
 STARBUCK'S DIRECTION. THE CALCULATIONS WERE TO BE
 SUBMITTED UNDER THE TENANT BUILD-OUT WHICH IS THIS
 PERMIT #20010876. THERE WERE PROVISOS PLACED ON THE
 APPROVED PLAN SHEET M.101 UNDER PERMIT #19090177
 STATING THAT THE CALCULATIONS WOULD BE PROVIDED UNDER
 THE TENANT BUILD-OUT. CURRENTLY AC CALCULATIONS HAVE
 BEEN SUBMITTED BUT NOT THE ENERGY CALCULATIONS AS
 REQUIRED BY SECTION C101.5 FBC EC. PLEASE SUBMIT AN
 ENERGY COMPLIANCE REPORT USING EITHER THE PRESCRIPTIVE
 OR PERFORMANCE BASED METHOD- SEE SECTION C401.2 FOR
 FURTHER COMPLIANCE INFORMATION.
  
 3) SHEETS M002 & M601: RTU-1 AT 10 TONS OF COOLING AND
 RTU-2 AT 8.5 TONS OF COOLING ARE OVERSIZED ACCORDING TO
 THE HEAT LOAD CALCS WHICH INDICATE 16 TONS OF COOLING
 REQUIRED- SECTION C403.2.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  