| 2020-02-07 13:32:33 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO |
| | THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4 |
| | |
| | 2. THE REAR GRAB BARS SHALL BE 36" MIN AND EXTEND 12" |
| | MIN FROM CENTERLINE OF THE TOILET AND 24" MIN ON THE |
| | OTHER SIDE. PER FBC ACC 604.5.2 |
| | |
| | 3. THE TOILET DISPENSER SHALL BE 15"- 48" MAX OFF |
| | FINISHED FLOOR AND 7" - 9" OFF THE FRONT OF THE TOILET. |
| | FBC ACC 604.7 |
| | |
| | 4. FULL PORT SHUT OFF ARE REQUIRED ON EACH DROP ON THE |
| | WATER SYSTEM. PER FBC PL 606.1(5) |
| | |
| | 5. PROVIDE SIZING CALCULATIONS FOR GREASE INTERCEPTOR. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |