Plan Review Notes
Plan Review Notes For Permit 20010876
Permit Number 20010876
Review Stop P
Sequence Number 1
Notes
Date Text
2020-02-07 13:32:331ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 2. THE REAR GRAB BARS SHALL BE 36" MIN AND EXTEND 12"
 MIN FROM CENTERLINE OF THE TOILET AND 24" MIN ON THE
 OTHER SIDE. PER FBC ACC 604.5.2
  
 3. THE TOILET DISPENSER SHALL BE 15"- 48" MAX OFF
 FINISHED FLOOR AND 7" - 9" OFF THE FRONT OF THE TOILET.
 FBC ACC 604.7
  
 4. FULL PORT SHUT OFF ARE REQUIRED ON EACH DROP ON THE
 WATER SYSTEM. PER FBC PL 606.1(5)
  
 5. PROVIDE SIZING CALCULATIONS FOR GREASE INTERCEPTOR.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]