| 2020-02-06 16:11:25 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010876 |
| | 2/6/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COMPLETE COOLING AND HEATING CALCULATIONS |
| | FOR THE RTU'S- SECTION C403.2.1 FBC EC. SHEET M001 |
| | CONTAINS ONLY PAGE 1 OF 3. |
| | |
| | 2) VERFIY THE NEW RTU'S WILL BE EQUIPPED WITH |
| | AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR O/A- |
| | SECTION C403.2.4.3 FBC EC. |
| | |
| | 3) SUBMIT AN ENERGY COMPLIANCE REPORT USING EITHER THE |
| | PRESCRIPTIVE OR PERFORMANCE BASED COMPLIANCE PATH AS |
| | REQUIRED BY SECTION C101.5 FBC EC. |
| | |
| | 4) M601: MIAMI-DADE NOA #14-1224.10 FOR THE AC |
| | CONDENSER STANDS HAS EXPIRED. PLEASE UPDATE THE NOA |
| | NUMBER AND SUBMIT THE DOCUMENT- RULE 9N-3 FAC. PLEASE |
| | NOTE THIS MAY BE A DEFERRED SUBMITTAL IF NECESSARY- |
| | SECTION 107.3.4.1 WPB. |
| | |
| | 5) G-004: SUBMIT MANUFACTURER'S SPECS FOR THE TURBO |
| | CHEF OVENS. PLEASE NOTE THAT IN ACCORDANCE WITH SECTION |
| | 507.3 WILL REQUIRE EITHER A TYPE II EXHAUST HOOD OR AN |
| | EXHAUST FAN SIZED AT .70 CFMS PER SF. THE DEFAULT |
| | SQUARE FOOTAGE NOTED IN THE CODE SECTION IS 100 SF. |
| | |
| | 6) M601: CORRECT THE LANDLORD PERMIT # B-19-232701-000 |
| | LISTED IN THE RTU SCHEDULE. THE LANDLORD'S SHELL PERMIT |
| | WAS #19090177. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |