| Plan Review Notes For Permit 20010871 |
| Permit Number |
20010871 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-03-25 08:00:01 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 3RD MECHANICAL REVIEW DENIED: | | | | | | REFER TO SECTION M1602.3 BALANCED RETURN AIR. 2017 | | | RESIDENTIAL CODE. | | | THE CFMS SHOWN ON THE PLANS COMPARED WITH THE CFMS | | | FROM THE A/C UNIT, AS SHOWN ON THE ENERGY CALCULATIONS, | | | ARE NOT BALANCED, THE SUBMITTED PLAN INDICATES A TOTAL | | | OF 1,160 CFM OF SUPPLY AIR AND THE ENERGY CALCULATIONS | | | INDICATE 750 CFM. | | | |
|