| 2020-02-18 09:04:31 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010870 |
| | 2/18/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M701, M801, & M802: THE PRINT ON THESE PLAN |
| | SHEETS IS TOO FAINT TO READ AND IS ILLEGIBLE. PLEASE |
| | PROVIDE CLEAR PLANS FOR REVIEW- SECTION 107.2.1 WPB. |
| | |
| | 2) M101: EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER |
| | SQUARE FOOT IS REQUIRED FOR THE LAB. PLEASE REFER TO |
| | SECTIONS 510.1 & 510.2 FBC M AND PROVIDE A NARRATIVE TO |
| | CLARIFY THE PROCESSES THAT OCCUR IN THE LAB. |
| | |
| | 3) M101 & M701: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | EXISTING FAN COIL UNITS- SECTION 107.2.1 WPB. |
| | |
| | 4) M101 & M701: REFER TO SECTION 809.2 FBC EX AND |
| | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS |
| | AND SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS |
| | OF OUTDOOR AIR. |
| | |
| | 5) M101: AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR |
| | GRAVITY, SHALL BE PROVIDED FOR O/A DUCTS SUPPLYING EACH |
| | FAN COIL UNIT- SECTION C403.2.4.3 FBC EC. |
| | |
| | 6) M101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | SUPPLY SYSTEMS OF THE EXISTING FAN COIL UNITS- SECTION |
| | 606.2.1 FBC M. PLEASE PROVIDE A SYMBOL AT ALL REQUIRED |
| | LOCATIONS AND INDICATE HOW THE DEVICES WILL BE |
| | SUPERVISED- SECTION 606.4.1 FBC M. |
| | |
| | 7) M101: RETURN GRILLS NOT SHOWN IN MANY OF THE ROOMS |
| | AND SPACES- SECTIONS 601.5 & 601.6 FBC M. |
| | |
| | 8) M101: PROVIDE AN EQUIPMENT PLAN AND SCHEDULE FOR THE |
| | CAFE. CLARIFY IF AN COOKING OPERATIONS WILL OCCUR THERE |
| | AND IF ANY COOKING APPLIANCES ARE TO BE INSTALLED- |
| | SECTION 107.2.1 WPB. PLEASE NOTE THAT EXHAUST |
| | VENTILATION MAY BE REQUIRED PER TABLE 403.3.1.1 AND |
| | SECTION 506 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |