| Plan Review Notes For Permit 20010870 |
| Permit Number |
20010870 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-11 16:45:48 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE ARE NO INDICATIONS THAT THERE ARE EXITS SIGNS | | | OVER THE TWO REAR EXIT DOORS. | | | | | | PER NFPA 101, CH 7, MEANS OF EGRESS | | | | | | 7.10.1.2 EXITS. | | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | | THAT OBVIOUSLY | | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | | BY AN APPROVED | | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | | ACCESS. | | | | | | PLEASE ENSURE COMPLIANCE | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|