| Plan Review Notes For Permit 20010867 |
| Permit Number |
20010867 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-22 13:04:23 | PLEASE PROVIDE PHOTOMETRIC FOR ALL BUIDLING ENTRANCES | | | AND FOR FRONT ASPHALT AREA (OFF SAPODILLA) BETWEEN CURB | | | AND COURTYARD- CAN USE EXTERNAL EXISTING SOURCES | | | SECTIONS OF COURTYARD THAT AREA AT 0.0 NEED TO BE | | | MINIMUM 0.6 | | | | | | PLEASE PROVIDE PHOTOMETRIC FOR DUMPSTER ENCLOSURE AREA- | | | MUST BE MINIMUM 0.6 | | | | | | SECTION 94-113 (B): | | | EXTERIOR LIGHTING. ALL BUILDINGS SHALL PROVIDE EXTERIOR | | | LIGHTING EVERY NIGHT FROM DUSK TO DAWN TO ILLUMINATE | | | BUILDING ENTRANCES, ADJACENT SIDEWALKS, AND PATHS, AT A | | | MINIMUM OF 0.6 FOOTCANDLES AS MEASURED AT THE BACK EDGE | | | OF THE CURB AND ONE FOOT ABOVE THE SIDEWALK. THIS | | | MEASUREMENT SHALL INCLUDE LIGHT EMANATING FROM PUBLIC | | | AND PRIVATE SOURCES. UNSHIELDED LIGHT FIXTURES SHALL BE | | | PROHIBITED. | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | 561 822 1426 | | | [email protected] |
|