| 2020-03-24 16:46:36 | 3/24/2020 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | 1) I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND |
| | THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF |
| | ANY GAS ON THIS PROPERTY. SINCE THERE IS NO RECORD OF |
| | GAS BEING PERMITED AT THIS ADDRESS PLEASE SUBMIT AN |
| | ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| | CUT SECTIONS OF PIPE PER 2017 FBC FUEL GAS, SECS. |
| | 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES SECS. |
| | G2413.4.1, G2413.4.2. WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 2)SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW GAS |
| | FRYER AND RANGE -FBC 2017 FG. SECTION 623.1 |
| | |
| | 3) SEPERATE PERMITS WILL BE REQUIRED FOR GREASE |
| | INTERCEPTOR, BACKLOW DEVICE, IRRIGATION, GENERAL |
| | PLUMBING, AND GAS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |