Plan Review Notes
Plan Review Notes For Permit 20010838
Permit Number 20010838
Review Stop M
Sequence Number 1
Notes
Date Text
2020-02-10 17:19:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010838
 2/10/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A2.1D & A2.1: PROVIDE A FRONT VIEW OF THE NEW
 COOKING LINE AND KITCHEN EXHAUST HOOD SHOWING THE
 REQUIRED CLEARANCES PER SECTION 507.4.1 FBC M:THE
 INSIDE LOWER EDGE OF CANOPY-TYPE TYPE I AND II
 COMMERCIAL HOODS SHALL OVERHANG OR EXTEND A HORIZONTAL
 DISTANCE OF NOT LESS THAN 6 INCHES (152 MM) BEYOND THE
 EDGE OF THE TOP HORIZONTAL SURFACE OF THE APPLIANCE ON
 ALL OPEN SIDES. THE VERTICAL DISTANCE BETWEEN THE FRONT
 LOWER LIP OF THE HOOD AND SUCH SURFACE SHALL NOT EXCEED
 4 FEET (1219 MM).
  
 2) A2.1D & A2.1: THE PHOTOS INDICATE THE HOOD DOES NOT
 HAVE THE REQUIRED 18" CLEARANCES TO THE COMBUSTIBLE
 DOOR TRIM AND THE ADJACENT DRYWALL. REFER TO SECTION
 507.2.6 FBC M: A TYPE I HOOD SHALL BE INSTALLED WITH A
 CLEARANCE TO COMBUSTIBLES OF NOT LESS THAN 18 INCHES
 (457 MM).
 EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM
 WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES
 PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND
 NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD
 AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA
 EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL
 DIRECTIONS FROM THE HOOD.
  
 3) A2.1: INDICATE HOW MAKEUP AIR IS BEING PROVIDED TO
 THE HOOD- SECTION 508.1 FBC M.
  
 4) A2.1: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED
 TO THE EXISTING GAS-FIRED 8 BURNER RANGE AND THE NEW
 GAS-FIRED FRYERS- SEE SECTION 304 FBC FG AND PROVIDE
 THE METHOD TO BE USED AND CALCULATIONS.
  
 5) A2.1: PROVIDE AN AIR BALANCE CALCULATION- SECTION
 508.1.2 FBC M.
  
 6) A2.1: NO MECHANICAL PLANS HAVE BEEN SUBMITTED
 HOWEVER THE CEILING IS GOING TO BE DEMOLISHED AND
 REPLACED. PLEASE SHOW ANY REQUIRED ALTERATIONS TO THE
 EXISTING DUCTWORK- SECTION 107.2.1 WPB.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW GAS
 FRYERS- SECTION 623.1 FBC FG.
  
 8) A SEPARATE PERMIT IS REQUIRED FOR MODIFICATIONS TO
 THE FIRE SUPPRESSION SYSTEM. PLEASE PLACE A NOTE ON THE
 PLAN ACCORDINGLY- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  