2020-02-15 21:54:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVICE NOTE ON PLAN STATING A SEPARATE FIRE ALARM
 PERMIT IS REQUIRED. FBC 105.1, FBC 107.2.1
  
 2. PROVIDE NOTE ON PLAN STATING A SEPARATE SITE
 LIGHTING PERMIT IS REQUIRED. FBC 105.1, FBC 107.2.1
  
 3. PROVIDE ACCURATE DIAGRAMS OF EXISTING SERVICES. ON
 POWER PLAN, IT IS ONLY LABELED AS "METER AND EXISTING
 PANEL" FOR BOTH SERVICES. ON ONE-LINE DIAGRAMS NO
 SERVICE DISCONNECTING MEANS ARE SHOWN AND PANELS ARE
 SHOWN AS MLO PANELS. SHOW SERVICE DISCONNECTING MEANS
 AND OCP SIZE. FBC 107.2.1
 NEC 215.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved