| 2020-02-15 21:54:22 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVICE NOTE ON PLAN STATING A SEPARATE FIRE ALARM |
| | PERMIT IS REQUIRED. FBC 105.1, FBC 107.2.1 |
| | |
| | 2. PROVIDE NOTE ON PLAN STATING A SEPARATE SITE |
| | LIGHTING PERMIT IS REQUIRED. FBC 105.1, FBC 107.2.1 |
| | |
| | 3. PROVIDE ACCURATE DIAGRAMS OF EXISTING SERVICES. ON |
| | POWER PLAN, IT IS ONLY LABELED AS "METER AND EXISTING |
| | PANEL" FOR BOTH SERVICES. ON ONE-LINE DIAGRAMS NO |
| | SERVICE DISCONNECTING MEANS ARE SHOWN AND PANELS ARE |
| | SHOWN AS MLO PANELS. SHOW SERVICE DISCONNECTING MEANS |
| | AND OCP SIZE. FBC 107.2.1 |
| | NEC 215.5 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |