Plan Review Notes
Plan Review Notes For Permit 20010798
Permit Number 20010798
Review Stop B
Sequence Number 1
Notes
Date Text
2020-01-24 10:31:08***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 THE SUBMITTED TEST REPORTS WERE NOT TESTED WITH VINYL
 FLOORING. FOR THE AREAS THAT ARE GOING TO HAVE VINYL
 FLOORING A DIFFERENT UNDERLAYMENT, SUCH AS PROFLEX LV
 200, WOULD BE MORE SUITABLE.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE
 AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492.
  