| Plan Review Notes For Permit 20010796 |
| Permit Number |
20010796 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-06 15:07:47 | PAVING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - | | | 1) DRAWINGS PREPARED BY AN ARCHITECT OR ENGINEER NEED | | | TO BE SIGNED AND SEALED BY THE DESIGNER. ELECTRONICALLY | | | SIGNED DRAWINGS CANNOT BE PRINTED - WHEN PRINTED OUT | | | THEY WILL NEED TO BE PHYSICALLY SIGNED AND SEALED BY | | | THE DESIGNER. | | | 2) DRAWINGS NEED TO BE ENLARGED TO BE CLEARLY SEEN - | | | FBC 107.2.1.3 | | | 3) PLEASE SHOW THE ACCESSIBLE ACCESS AISLE NEXT TO THE | | | ACCESSIBLE PARKING SPACE TO BE THE FULL LENGTH OF THE | | | PARKING SPACE - FBC ACCESSIBILITY 502.3.2 | | | 4) BICYCLE PARKING CANNOT BE SHOWN IN THE ACCESSIBLE | | | PARKING ACCESS AISLE PER FBC ACCESSIBILITY 502.3 | | | 5) BUILDING PERMIT APPLICATION STATES "SITE WORK, | | | CONCRETE AND ASPHALT PAVING" - PLEASE REMOVE OR CROSS | | | OUT ALL OTHER DETAILS AND DRAWINGS NOT RELATED TO THE | | | WORK DESCRIPTION ON THE BUILDING PERMIT APPLICATION. | | | FBC WPB AMENDMENTS 105.1 | | | | | 2020-01-30 07:52:06 | MISC 2 |
|