2020-01-28 17:54:07PLAN REVIEW - PLUMBING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFY THE DISH WASHER ON SANITARY ISO.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. TUB AND SHOWER AT MASTER BATH GROUP SHALL BE
 INDEPENDENTLY CONNECTED TO WET VENT.
 P3108.1 HORIZONTAL WET VENT PERMITTED.
 EACH FIXTURE DRAIN SHALL CONNECT HORIZONTALLY TO THE
 HORIZONTAL BRANCH BEING WET VENTED OR SHALL HAVE A DRY
 VENT.
  
 3. HORIZONTAL WET VENT SHALL INCREASE IN SIZE TO 3
 INCHES AFTER INDEPENDENTLY CONNECTING SHOWER FROM
 M-BATH GROUP.
 TABLE P3801.3
  
 4. WASHING MACHINE MUST CONNECT TO THE HORIZONTAL WET
 VENT DOWNSTREAM OF THE WATER CLOSET FROM M-BATH GROUP.