| 2020-01-31 10:49:26 | PLAN REVIEW - ELECTRIC |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SMOKE ALARM AT BATH #3 APPEARS TOO CLOSE TO BATH. |
| | R314.3 LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | |
| | SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET |
| | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A |
| | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS |
| | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY |
| | SECTION R314.3 |
| | |
| | 2. DISHWASHER OUTLET SHALL BE GFI PROTECTED. |
| | |
| | PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D); |
| | FBC RE E3902.10 |
| | |
| | 3. OUTLETS IN GARAGE SHALL BE GFI PROTECTED. |
| | |
| | GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE OUTLETS |
| | IN GARAGE. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| | E3902.2 |
| | |
| | 4. PROVIDE NOTE ON PLAN - PROVIDE COMPLIANCE: A MINIMUM |
| | OF 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A |
| | MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY |
| | LAMPS. A NOTE WILL SUFFICE. FBC EC C405.1, R404.1 |
| | |
| | 5. PROVIDE NOTE ON PLAN - AFCI PROTECTION. ALL BRANCH |
| | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING, POWER |
| | OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI |
| | AND GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8, |
| | 210.12; FBC RE E3902.16; FBC EX 607.1.1 OR 801.1, |
| | 801.2, OR 901.2 AS APPLICABLE. |
| | |
| | 6. PROVIDE INTERSYSTEM BONDING AT SERVICE. |
| | |
| | PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | |
| | 7. DISCONNECT IS REQUIRED AT EXTERIOR OF STRUCTURE - |
| | FEEDER CONDUCTORS EXCEED 8 FEET. |
| | |
| | NEC 230.70 |
| | |
| | NOTICE: THE #1/0 THHN GROUNDED CONDUCTOR FROM |
| | DISCONNECT TO PANEL IS OVERSIZED. A #6 COPPER CONDUCTOR |
| | WOULD BE CODE COMPLIANT. |
| | |
| | TABLE 3908.12 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |