| Plan Review Notes For Permit 20010663 |
| Permit Number |
20010663 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-02-26 08:56:02 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 603.1/FBC B 1207.2/FBC B 1207.3, IT APPEARS THAT | | | USING THE SELECTED FLOORING UNDERLAYMENT (PRO FLEX RCU | | | 250) HAS ONLY BEEN APPROVED FOR 8" THICK SLABS NOT 6". | | | | | | PLEASE PROVIDE THE ASTM E- 84 FLAME SPREAD, ASTM E - 90 | | | SOUND TRANSMISSION LOSS, AND ASTM E - 492 IMPACT SOUND | | | TRANSMISSION LOSS SPECIFICATIONS FOR 6" THICK SLABS OR | | | PROVIDE AN ALTERNATE PRODUCT THAT HAS BEEN APPROVED FOR | | | THE 6" SLABS. |
|