Plan Review Notes
Plan Review Notes For Permit 20010651
Permit Number 20010651
Review Stop P
Sequence Number 4
Notes
Date Text
2020-06-02 08:19:34REVIEWED BY JERRY SMITH.
 20010651 931 VILLAGE BLVD
  
 PLUMBING COMMENTS: APPROVED W/PROVISO
 PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE AS A
 DEFERRED SUBMITTAL, REVISED PLAN SHEETS NOTED IN THE
 COMMENTS BELOW. SUBMITTAL SHALL BE SUBMITTED, APPROVED
 AND ON SITE PRIOR TO FIRST INSPECTION. PROCEED AT YOUR
 OWN RISK.
 1. REGARDING THE COMMENT FROM REVIEW DATED 5/7/2020;
 SHOW THE LENGTH OF THE STANDARD WATER CLOSET
 COMPARTMENTS. COMPLY WITH FBC-PLUMBING SEC.405.3.1. SEE
 REDLINED COMMENTS ON A-1.
 2.SECOND REQUEST; THE LAVATORIES AND HAND SINKS SHALL
 BE DRAWN AS BEING STACKED AND VENTED ON THE SANITARY
 RISER DIAGRAM. AS DRAWN, THEY DO NOT COMPLY WITH THE
 PLUMBING CODE. SEE REDLINED EXAMPLE ON MARKED UP PLAN
 SHEET P-1. IT IS UNDERSTOOD THAT WHEN DRAWING 30/60 IN
 CADD PRESENTS CHALLENGES WHEN IT COMES TO SHOWING
 HORIZONTAL 45 DEGREE ANGLES AND SUBSEQUENT VERTICAL
 LINES. A DETAIL SIMILAR TO THE PROVIDED REDLINED
 EXAMPLE PROVIDED FOR CLARIFICATION IS ACCEPTABLE.
 3.REGARDING THE COMMENT FROM REVIEW DATED 5/7/2020; THE
 HOT WATER RECIRCULATION SYSTEM SHALL COMPLY WITH
 FBC-PLUMBING SEC.607.2.2. 607.2.2. WHERE A THERMOSTATIC
 MIXING VALVE IS USED IN A SYSTEM WITH A HOT WATER
 RECIRCULATING PUMP, THE HOT WATER OR TEMPERED WATER
 RETURN LINE SHALL BE ROUTED TO THE COLD WATER INLET
 PIPE OF THE WATER HEATER AND THE COLD WATER INLET PIPE
 OR THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC
 MIXING VALVE.
 SEE PLAN SHEET P-2 TYPICAL HOT PIPING DETAIL
 (COMMERCIAL) INDICATES A STORAGE TYPE WATER HEATER AND
 A THERMOSTATIC MIXING VALVE (EQUAL TO LEONARD TM-26-LF;
 EQUAL TO IS NOT PERMITTED) SENDING 110 DEGREE WATER TO
 FIXTURES (WHICH ACCORDING TO THE DETAIL WOULD INCLUDE
 THE KITCHEN FIXTURES AS WELL AS THE BATH FIXTURES.
 COMPLIANCE WITH FBC PL 416.5 PROVIDING TEMPERATURE
 LIMITING DEVICES COMFORMING TO ASSE 1070 FOR PUBLIC
 BATHROOM LAVATORIES WILL STILL BE REQUIRED. THE GAS
 WATER HEATER PIPING DETAIL AND PIPING PLANS INDICATE
 GAS TANKLESS WATER HEATERS AND NO THERMOSTATIC MIXING
 VALVE. THERE IS A SPECIFICATION FOR WATTS
 LF-1170/LFL-1170 THERMOSTATIC MIXING VALVE CONFORMING
 TO ASSE 1017.
 PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE PLANS AND
 DETAILS COMPLETE INSTALLATION DIRECTION INCLUDING
 COMPLIANCE WITH FBC PL 416.5 (PROVIDING TEMPERATURE
 LIMITING DEVICES COMFORMING TO ASSE 1070 FOR PUBLIC
 BATHROOM LAVATORIES). REMOVE ALL ITEMS AND DIRECTION
 THAT DO NOT PERTAIN TO THE PROJECT.
 REFER TO REDLINED P-2.
 4.IN ACCORDANCE WITH FBC PL SECTION 608, PROVIDE
 BACKFLOW PREVENTIVE DEVICES FOR THE FOLLOWING ITEMS;
 INCLUDE DEVICE TYPE FOR EACH APPLICATION (SEE FBC PL
 TABLE 608.1): SEE REDLINED P2-1.
  
 A.SODA DISPENSERS AND GUNS
 B.MOP SINK FAUCETS
 C.ICE MAKERS
 D.ICE STORAGE BINS
  
 5.PER FBC PL 604.9, SPECIFY AND PROVIDE WATER HAMMER
 ARRESTORS CONFORMING TO ASSE 1010 WHERE QUICK CLOSING
 VALVES ARE UTILIZED INCLUDING BUT NOT LIMITED TO
 DISHWASHERS AND ICE MAKERS. SEE REDLINED P2-1.
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20010651 931 VILLAGE BLVD
  
  