| Plan Review Notes For Permit 20010651 |
| Permit Number |
20010651 |
|
| Review Stop |
P-GREASE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-05-07 15:17:40 | 1) THE SUBMITTED GREASE INTERCEPTOR SPECIFICATIONS CALL | | | OUT 1200 GALLON TANKS BUT THE PLANS SHOW 1250 GALLON | | | TANKS. CLARIFY. | | | 2) THE CITY STANDARD GREASE INTERCEPTOR DRAWING GS-7 | | | SHOWS THE SIZE OF THE BAFFLE HOLE AS 8 INCH BUT THE | | | SUBMITTED SPECIFICATION SHOWS THE BAFFLE HOLE AS 5 | | | INCH. CLARIFY. | | | 3) THE SUBMITTED GREASE INTERCEPTOR SPECIFICATIONS SHOW | | | THE LOCATION OF THE BAFFLE HOLE AT 3 FEET 6 INCHES | | | ABOVE THE BOTTOM OF THE INTERCEPTOR AND THE CITY | | | STANDARD DRAWING SHOWS THE BAFFLE HOLE AT 12 INCHES | | | ABOVE THE BOTTOM OF THE INTERCEPTOR. CLARIFY. | | | 4) THE SUBMITTED GREASE INTERCEPTOR SPECIFICATIONS | | | SHOWS A 6 INCH INLET AND OUTLET ON THE INTERCEPTORS YET | | | THE SANITARY RISER SHOWS A 4 INCH LINE ENTERING AND | | | EXITING THE INTERCEPTORS. THIS WILL CREATE A REDUCTION | | | IN PIPE SIZE ON THE OUTLET OF THE INTERCEPTORS WHICH | | | VIOLATES FBC-PLUMBING SEC.704.2. | | | 5) SHT. P1 - THE GREASE INTERCEPTOR CALCULATIONS REFER | | | TO A SECTION 1003.5.1. THERE IS NO SUCH SECTION IN THE | | | PLUMBING CODE. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|