| 2020-05-07 15:01:57 | 1) SHT. A1 - SHOW THE LENGTH AND WIDTH DIMENSIONS OF |
| | THE HANDICAP ACCESSIBLE TOILET STALL IN THE WOMEN'S |
| | RESTROOM. COMPLY WITH FBC-ACCESS. SECS.604.3 AND 606.2 |
| | FOR THE REQUIRED CLEAR FLOOR SPACES. |
| | 2) WHERE LAVATORIES ARE PROVIDED, AT LEAST ONE SHALL |
| | COMPLY WITH SEC. 606 OF THE FBC-ACCESS. AND SHALL NOT |
| | BE LOCATED IN A TOILET COMPARTMENT PER FBC-ACCESS. |
| | SEC.213.3.4.SHOW THIS ON THE PLAN. |
| | 3) SHOW THE LENGTH OF THE STANDARD WATER CLOSET |
| | COMPARTMENTS. COMPLY WITH FBC-PLUMBING SEC.405.3.1. |
| | 4) THE LAVATORIES AND HAND SINKS SHALL BE DRAWN AS |
| | BEING STACKED AND VENTED ON THE SANITARY RISER DIAGRAM. |
| | AS DRAWN, THEY DO NOT COMPLY WITH THE PLUMBING CODE. |
| | 5) THE ICE BINS AND ICEMAKER CANNOT DISCHARGE TO THE |
| | GREASE WASTE SYSTEM PER FBC-PLUMBING SEC. 1003.2. |
| | 6) SIZE ALL SECTIONS OF THE VENT SYSTEM FOR THE |
| | SANITARY SYSTEM. COMPLY WITH FBC-PLUMBING SEC.906.1. |
| | 7) VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL BE |
| | INCREASED ONE PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH |
| | OF THE VENT PIPE. FBC-PLUMBING SEC.906.2. |
| | 8) THE SANITARY RISER DOES NOT CORRELATE WITH THE |
| | SANITARY PLAN. VENTS ARE NOT SHOWN ON THE SANITARY |
| | PLAN. CLARIFY. |
| | 9) THE MOP SINK ON THE GREASE WASTE SYSTEM REQUIRES AN |
| | INDIVIDUAL VENT.AS DRAWN, IT IS CREATING A HORIZONTAL |
| | WET VENT AND ONLY FIXTURES IN A BATHROOM GROUP ARE |
| | PERMITTED TO DISCHARGE INTO A WET VENT.FBC-PLUMBING |
| | SEC.912.1. |
| | 10) SHT.P2 - WATER PLUMBING NOTES - PVC CANNOT BE USED |
| | FOR THE WATER DISTRIBUTION SYSTEM PER FBC-PLUMBING SEC. |
| | 605.4 AND TABLE 605.4. DELETE THIS NOTE. |
| | 11) SUBMIT AN EXPANDED WATER RISER FOR REVIEW. THE |
| | SUBMITTED WATER RISER IS VERY DIFFICULT TO REVIEW. THE |
| | ARROWS AND SMALL RECTANGULAR FIGURES OBSCURE THE |
| | PIPING. WPB AMEND.TO FBC SEC. 107.2.1. |
| | 12) CLEARLY SHOW THE HOT WATER RETURN LINE ON THE |
| | REQUESTED WATER RISER DIAGRAM. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 13) THE HOT WATER RECIRCULATION SYSTEM SHALL COMPLY |
| | WITH FBC-PLUMBING SEC.607.2.2. 607.2.2. WHERE A |
| | THERMOSTATIC MIXING VALVE IS USED IN A SYSTEM WITH A |
| | HOT WATER RECIRCULATING PUMP, THE HOT WATER OR TEMPERED |
| | WATER RETURN LINE SHALL BE ROUTED TO THE COLD WATER |
| | INLET PIPE OF THE WATER HEATER AND THE COLD WATER INLET |
| | PIPE OR THE HOT WATER RETURN CONNECTION OF THE |
| | THERMOSTATIC MIXING VALVE. |
| | 14) THE HOT WATER PIPING SHALL BE INSULATED IN ITS |
| | ENTIRETY. THE INSULATION SHALL COMPLY WITH FBC-ENERGY |
| | TABLE C403.2.10. |
| | 15) THE ENERGY CALCULATIONS CALL OUT AN ELECTRIC WATER |
| | HEATER UNDER THE "PLANT COMPLIANCE" HEADING WITH A SIZE |
| | AS 23. THIS STRUCTURE HAS 2 TANKLESS GAS WATER HEATERS. |
| | CLARIFY. |
| | 16) THE ENERGY CALCULATIONS CALL OUT A GAS STORAGE |
| | WATER HEATER UNDER THE "WATER HEATER COMPLIANCE" |
| | HEADING. THERE ARE TANKLESS WATER HEATERS ON THIS |
| | PROJECT.CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |