Plan Review Notes For Permit 20010651
Permit Number 20010651
Review Stop P
Sequence Number 3
Notes
Date Text
2020-05-07 15:01:571) SHT. A1 - SHOW THE LENGTH AND WIDTH DIMENSIONS OF
 THE HANDICAP ACCESSIBLE TOILET STALL IN THE WOMEN'S
 RESTROOM. COMPLY WITH FBC-ACCESS. SECS.604.3 AND 606.2
 FOR THE REQUIRED CLEAR FLOOR SPACES.
 2) WHERE LAVATORIES ARE PROVIDED, AT LEAST ONE SHALL
 COMPLY WITH SEC. 606 OF THE FBC-ACCESS. AND SHALL NOT
 BE LOCATED IN A TOILET COMPARTMENT PER FBC-ACCESS.
 SEC.213.3.4.SHOW THIS ON THE PLAN.
 3) SHOW THE LENGTH OF THE STANDARD WATER CLOSET
 COMPARTMENTS. COMPLY WITH FBC-PLUMBING SEC.405.3.1.
 4) THE LAVATORIES AND HAND SINKS SHALL BE DRAWN AS
 BEING STACKED AND VENTED ON THE SANITARY RISER DIAGRAM.
 AS DRAWN, THEY DO NOT COMPLY WITH THE PLUMBING CODE.
 5) THE ICE BINS AND ICEMAKER CANNOT DISCHARGE TO THE
 GREASE WASTE SYSTEM PER FBC-PLUMBING SEC. 1003.2.
 6) SIZE ALL SECTIONS OF THE VENT SYSTEM FOR THE
 SANITARY SYSTEM. COMPLY WITH FBC-PLUMBING SEC.906.1.
 7) VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL BE
 INCREASED ONE PIPE SIZE FOR THE ENTIRE DEVELOPED LENGTH
 OF THE VENT PIPE. FBC-PLUMBING SEC.906.2.
 8) THE SANITARY RISER DOES NOT CORRELATE WITH THE
 SANITARY PLAN. VENTS ARE NOT SHOWN ON THE SANITARY
 PLAN. CLARIFY.
 9) THE MOP SINK ON THE GREASE WASTE SYSTEM REQUIRES AN
 INDIVIDUAL VENT.AS DRAWN, IT IS CREATING A HORIZONTAL
 WET VENT AND ONLY FIXTURES IN A BATHROOM GROUP ARE
 PERMITTED TO DISCHARGE INTO A WET VENT.FBC-PLUMBING
 SEC.912.1.
 10) SHT.P2 - WATER PLUMBING NOTES - PVC CANNOT BE USED
 FOR THE WATER DISTRIBUTION SYSTEM PER FBC-PLUMBING SEC.
 605.4 AND TABLE 605.4. DELETE THIS NOTE.
 11) SUBMIT AN EXPANDED WATER RISER FOR REVIEW. THE
 SUBMITTED WATER RISER IS VERY DIFFICULT TO REVIEW. THE
 ARROWS AND SMALL RECTANGULAR FIGURES OBSCURE THE
 PIPING. WPB AMEND.TO FBC SEC. 107.2.1.
 12) CLEARLY SHOW THE HOT WATER RETURN LINE ON THE
 REQUESTED WATER RISER DIAGRAM. WPB AMEND. TO FBC SEC.
 107.2.1.
 13) THE HOT WATER RECIRCULATION SYSTEM SHALL COMPLY
 WITH FBC-PLUMBING SEC.607.2.2. 607.2.2. WHERE A
 THERMOSTATIC MIXING VALVE IS USED IN A SYSTEM WITH A
 HOT WATER RECIRCULATING PUMP, THE HOT WATER OR TEMPERED
 WATER RETURN LINE SHALL BE ROUTED TO THE COLD WATER
 INLET PIPE OF THE WATER HEATER AND THE COLD WATER INLET
 PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE.
 14) THE HOT WATER PIPING SHALL BE INSULATED IN ITS
 ENTIRETY. THE INSULATION SHALL COMPLY WITH FBC-ENERGY
 TABLE C403.2.10.
 15) THE ENERGY CALCULATIONS CALL OUT AN ELECTRIC WATER
 HEATER UNDER THE "PLANT COMPLIANCE" HEADING WITH A SIZE
 AS 23. THIS STRUCTURE HAS 2 TANKLESS GAS WATER HEATERS.
 CLARIFY.
 16) THE ENERGY CALCULATIONS CALL OUT A GAS STORAGE
 WATER HEATER UNDER THE "WATER HEATER COMPLIANCE"
 HEADING. THERE ARE TANKLESS WATER HEATERS ON THIS
 PROJECT.CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW