| 2020-05-08 08:30:40 | 1) SHOW THE DISTANCE OF THE TANKLESS WATER HEATER FROM | | | THE DOOR. THE WATER HEATER SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION MANUAL. | | | MOST MANUFACTURERS REQUIRED A MINIMUM OF 4 FEET FROM | | | OPERABLE DOORS OR WINDOWS. | | | 2) THE SCREEN ON THE COMBUSTION AIR LOUVER SHALL HAVE A | | | MESH SIZE NO SMALLER THAN 1/4 INCH IN SIZE PER FBC-FUEL | | | GAS SEC. 304.10. | | | 3) SHOW THE DISTANCE FROM ALL REGULATORS TO THE | | | APPLIANCE INCLUDING THE DROPS TO THE APPLIANCE. | | | 4) SOME OF THE SEDIMENT TRAPS AS DRAWN ARE WILL NOT | | | WORK. REFER TO FIGURE 408.4 OF FBC-FUEL GAS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|