Plan Review Notes
Plan Review Notes For Permit 20010651
Permit Number 20010651
Review Stop G
Sequence Number 3
Notes
Date Text
2020-05-08 08:30:401) SHOW THE DISTANCE OF THE TANKLESS WATER HEATER FROM
 THE DOOR. THE WATER HEATER SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION MANUAL.
 MOST MANUFACTURERS REQUIRED A MINIMUM OF 4 FEET FROM
 OPERABLE DOORS OR WINDOWS.
 2) THE SCREEN ON THE COMBUSTION AIR LOUVER SHALL HAVE A
 MESH SIZE NO SMALLER THAN 1/4 INCH IN SIZE PER FBC-FUEL
 GAS SEC. 304.10.
 3) SHOW THE DISTANCE FROM ALL REGULATORS TO THE
 APPLIANCE INCLUDING THE DROPS TO THE APPLIANCE.
 4) SOME OF THE SEDIMENT TRAPS AS DRAWN ARE WILL NOT
 WORK. REFER TO FIGURE 408.4 OF FBC-FUEL GAS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW