Plan Review Notes
Plan Review Notes For Permit 20010651
Permit Number 20010651
Review Stop Z
Sequence Number 2
Notes
Date Text
2020-04-15 10:21:28FAILED
  
 1) REPEAT COMMENT: THE PLANS SHOW A NEW 5 TON RTU, A
 NEW 12.5 TON RTU, 2 NEW ROOF FANS AND A NEW MAU ARE ALL
 SHOWN ON THE ROOF. ALL NEW MECHANICAL EQUIPMENT SHALL
 BE SCREENED FROM VIEW OF THE PUBLIC. PROVIDE DRAWINGS
 TO VERIFY THAT THE FULL HEIGHT OF THE EQUIPMENT IS
 SCREENED FROM VIEW. THIS INCLUDES THE REAR OF THE SITE
 (KEISER UNIVERSITY). ---- THIS IS NEW EQUIPMENT, SO PER
 THE DEVELOPMENT ORDER FOR VILLAGE COMMONS ADOPTED IN
 2016, IT NEEDS TO BE SCREENED.
  
 CONTACT ERIC SCHNEIDER @ (562) 822-1446
 [email protected]
  