| 2020-04-16 11:56:12 | REVIEWED BY JERRY SMITH. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20010651 931 VILLAGE BLVD |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | PLAN SHEET P-1 |
| | 1. CIRCUIT VENT IS REQUIRED FOR WOMEN? S THREE WATER |
| | CLOSETS OR ELSE WET VENT THE ACCESSIBLE WATER CLOSET |
| | WITH THE ACCESSIBLE LAVATORY. SEE FBC PL 912.1 AND |
| | 914.1. |
| | 2. INTERCEPTOR: PER WPB FBC 107.2.1, PROVIDE A DETAIL |
| | AND MANUFACTURER?S SPECIFICATION OF THE GREASE |
| | INTERCEPTOR(S) SHOWING COMPLIANCE WITH WPB PUBLIC WORKS |
| | DEPARTMENT DOCUMENT GS-7 (CONCRETE GRAVITY INTERCEPTOR) |
| | OR GS-7.1 (HYDRO MECHANICAL GRAVITY INTERCEPTOR) |
| | INDICATE ON PLAN AND RISER SANITARY DIAGRAMS. PLEASE |
| | NOTE THAT AS STATED ON GS-7, THE MAXIMUM SIZE CONCRETE |
| | INTERCEPTOR SHALL BE 1250 GALLONS AND BASED ON YOUR |
| | CALCULATIONS WOULD REQUIRE MULTIPLE TANKS IN SERIES AND |
| | YOUR CALCULATIONS WOULD NEED TO REFLECT THE SAME. |
| | |
| | PLAN SHEET P-2 |
| | 1. RECIRCULATING PUMP(S) ARE INDICATED ON PLAN AND |
| | RISER DRAWINGS; AS REQUIRED BY FBC PL 607.2, THE |
| | DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, FROM |
| | THE SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRE |
| | HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET. |
| | RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING |
| | SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED |
| | WATER. |
| | 2. PER WPB FBC 107.2.1, PROVIDE DETAIL OF RECIRCULATING |
| | PUMP(S) AND CONNECTION(S) TO WATER HEATERS. |
| | 3. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION AND MANUAL FOR RECIRCULATING PUMP(S). |
| | 4. PER WPB FBC 107.2.1, PROVIDE IN PLAN AND RISER |
| | DIAGRAMS RECIRCULATING PIPE ROUTING AND SIZING. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20010651 931 VILLAGE BLVD |
| | |
| | |