Plan Review Notes
Plan Review Notes For Permit 20010651
Permit Number 20010651
Review Stop P
Sequence Number 2
Notes
Date Text
2020-04-16 11:56:12REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20010651 931 VILLAGE BLVD
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 PLAN SHEET P-1
 1. CIRCUIT VENT IS REQUIRED FOR WOMEN? S THREE WATER
 CLOSETS OR ELSE WET VENT THE ACCESSIBLE WATER CLOSET
 WITH THE ACCESSIBLE LAVATORY. SEE FBC PL 912.1 AND
 914.1.
 2. INTERCEPTOR: PER WPB FBC 107.2.1, PROVIDE A DETAIL
 AND MANUFACTURER?S SPECIFICATION OF THE GREASE
 INTERCEPTOR(S) SHOWING COMPLIANCE WITH WPB PUBLIC WORKS
 DEPARTMENT DOCUMENT GS-7 (CONCRETE GRAVITY INTERCEPTOR)
 OR GS-7.1 (HYDRO MECHANICAL GRAVITY INTERCEPTOR)
 INDICATE ON PLAN AND RISER SANITARY DIAGRAMS. PLEASE
 NOTE THAT AS STATED ON GS-7, THE MAXIMUM SIZE CONCRETE
 INTERCEPTOR SHALL BE 1250 GALLONS AND BASED ON YOUR
 CALCULATIONS WOULD REQUIRE MULTIPLE TANKS IN SERIES AND
 YOUR CALCULATIONS WOULD NEED TO REFLECT THE SAME.
  
 PLAN SHEET P-2
 1. RECIRCULATING PUMP(S) ARE INDICATED ON PLAN AND
 RISER DRAWINGS; AS REQUIRED BY FBC PL 607.2, THE
 DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, FROM
 THE SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRE
 HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET.
 RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING
 SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED
 WATER.
 2. PER WPB FBC 107.2.1, PROVIDE DETAIL OF RECIRCULATING
 PUMP(S) AND CONNECTION(S) TO WATER HEATERS.
 3. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION AND MANUAL FOR RECIRCULATING PUMP(S).
 4. PER WPB FBC 107.2.1, PROVIDE IN PLAN AND RISER
 DIAGRAMS RECIRCULATING PIPE ROUTING AND SIZING.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  