| 2020-04-14 12:29:11 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20010651 |
| | 4/14/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M3: THE NOTE BELOW THE NEW AC CALCULATIONS |
| | INDICATES 40 TONS OF COOLING REQUIRED AND PROVIDED, |
| | HOWEVER IT APPEARS THAT THE LATENT LOAD SHOWN IN THE |
| | CALCS- 150640 BTUH WAS NOT ADDED INTO THE CALCULATION |
| | WITH THE SENSIBLE LOAD- 484812 BTUH WHICH EQUALS A |
| | TOTAL HEAT LOAD OF 635452 BTUH OR 53 TONS. THE |
| | CALCULATIONS ALSO SHOW A VERY LOW BTUH LOAD FOR |
| | OCCUPANTS AND PLANTS AT 1416 TOTAL BTUH COMBINED |
| | SENSIBLE AND LATENT. FOR AN OCCUPANT LOAD OF 172 |
| | PERSONS, THAT WOULD AMOUNT TO 8.2 BTUH FOR EACH |
| | OCCUPANT WHICH IS FAR LOWER THAN AN AVERAGE 250-300 |
| | LOAD PER PERSON.BASED ON THE CALCULATIONS IT APPEARS |
| | VERY POSSIBLE THAT ONE OR ALL OF THE SYSTEMS SELECTED |
| | ARE UNDERSIZED. PLEASE REVIEW AND CORRECT THE THE |
| | CALCULATIONS- SECTION C403.2.1 FBC EC. |
| | |
| | 2) M1: AS PREVIOUSLY REQUESTED IN COMMENT #4D OF THE |
| | 1ST REVIEW, PLEASE INDICATE HOW THE O/A AT THE RTU |
| | INTAKES WILL BE CONTROLLED USING EITHER A MOTORIZED OR |
| | GRAVITY DAMPER- SECTION C403.2.4.3 FBC EC. |
| | |
| | 3) THE SUBMITTED ENERGYGAUGE/ASHRAE 90.1 COMPLIANCE |
| | FORM REQUIRES THE DIGITAL SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL WHO PREPARED THE DOCUMENT- FL. |
| | STATUTE 471.025 AND SECTION 61G15-23.005 FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | COMMENT #5 FROM THE 1ST REVIEW PRINTED BELOW STILL |
| | EXISTS. THE COMBUSTION AIR CALCULATION INDICATES THE |
| | COMBUSTION AIR TO BE PROVIDED BY THE MUA, PLEASE NOTE |
| | THAT THE MAKEUP AIR FROM THE MUA IS DEDICATED TO |
| | REPLACE EXHAUSTED AIR FROM THE HOOD, AND CANNOT BE USED |
| | AS A COMBUSTION AIR SOURCE- SEE SECTIONS 304.9 AND |
| | 304.9.3 FBC FG. |
| | |
| | 5) M1: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO |
| | THE COOKING APPLIANCES AND PROVIDE CALCULATIONS- SEE |
| | SECTION 304 FBC FG. |
| | |
| | COMMENT # 6 FROM THE 1ST REVIEW PRINTED BELOW HAS NOT |
| | BEEN ADDRESSED. PLEASE PROVIDE THE COST BREAKDOWN AND |
| | PLACE A NOTE ON THE PLAN TO INDICATE THE REQUIRED |
| | SEPARATE PERMITS AND PLANS. |
| | |
| | 6) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE |
| | KITCHEN EXHAUST HOOD, FIRE SUPPRESSION SYSTEM, AND |
| | WALKIN COOLERS AND FREEZERS. PLEASE PROVIDE A COST |
| | BREAKDOWN FOR THE ENTIRE PROJECT THAT SHOWS THE COSTS |
| | OF THESE ITEMS REMOVED FOM THE TOTAL VALUE OF THE |
| | PROPOSED RESTAURANT- SECTIONS 107.2.1 & 109.3 WPB. |
| | |
| | COMMENT #7 THE 1ST REVIEW PRINTED BELOW HAS NOT BEEN |
| | ADDRESSED. PLEASE NOTE IT WOULD APPEAR BY THE LACK OF |
| | RESPONSE THAT AN MUA WILL HAVE TO BE INSTALLED UNDER |
| | THE SEPARATE HOOD PERMIT. |
| | |
| | 7) ADVISORY: CONCERNING THE KITCHEN HOOD SYSTEM, IT IS |
| | IMPORTANT TO NOTE THE MAKEUP AIR TEMPERATURE |
| | REQUIREMENT UNDER SECTION 508.1.1 FBC M BECAUSE IT MAY |
| | IMPACT THE MAIN RESTAURANT PLANS. 508.1.1 MAKEUP AIR |
| | TEMPERATURE. |
| | |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| | DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |