Plan Review Notes
Plan Review Notes For Permit 20010651
Permit Number 20010651
Review Stop G
Sequence Number 2
Notes
Date Text
2020-04-17 07:36:00REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20010651 931 VILLAGE BLVD
  
 2ND REVIEW
 GAS COMMENTS: DENIED
 1. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR THE REGULATORS HAVE NOT BEEN PROVIDED AS
 PREVIOUSLY REQUESTED. PER WPB FBC 107.2.1 PROVIDE THE
 SAME; SHOW APPROVAL FOR OUTDOOR USE WHERE APPLICABLE.
 ADDITIONALLY, SHOW VENTING OF THE OF THE INTERIOR
 REGULATOR(S) INCLUDING VENT PIPE SIZES, ROUTING AND
 TERRMINATION OR, INDICATE THE USE OF A VENT ELIMINATOR
 IF MANUFACTURER ALLOWS AND SPECIFY THE SAME.
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER FBC FG
 SEC. 304. THE COMBUSTION AIR CALCULATION INDICATES THE
 COMBUSTION AIR TO BE PROVIDED BY THE MUA, PLEASE NOTE
 THAT THE MAKEUP AIR FROM THE MUA IS DEDICATED TO
 REPLACE EXHAUSTED AIR FROM THE HOOD, AND CANNOT BE USED
 AS A COMBUSTION AIR SOURCE PER FBC FG 304.9 AND
 304.9.3.
 3. CHINESE STOVE: PER WPB FBC 107.2.1, INDICATE ON THE
 EQUIPMENT SUBMITTAL THE APPLICABLE BURNERS THAT ADD UP
 TO 700K BTUS NOTED ON THE SCHEDULE.
 4. FOUR BURNER RANGE: PER WPB FBC 107.2.1, INDICATE ON
 THE EQUIPMENT SUBMITTAL THE CORRECT MODEL FOR THE UNIT.
 5. PER WPB FBC 107.2.1, PROVIDE DETAIL OF EMERGENCY
 SHUT OFF VALVE ASSEMBLY WITH MANUAL SHUT OFF VALVE,
 REGULATOR, REQUIRED UNIONS AND CAPPED TEES AS REQUIRED
 BY FBC FG 409.4, 410.2 AND NFPA 96 SECTIONS 10.4 AND
 10.5. PROVIDE NOTE ?SHALL BE INSTALLED BELOW CEILING?.
 CLOUD AFFECTED AREA ON RISER DIAGRAM AND INDICATE
 REFERENCE TO SAID DETAIL.
 6. THERE ARE MULTIPLE VALVES SHOWN AHEAD OF THE MP
 REGULATOR FOR THE WATER HEATERS. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20010651 931 VILLAGE BLVD
  
  