Plan Review Notes
Plan Review Notes For Permit 20010651
Permit Number 20010651
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-30 11:11:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010651
 1/30/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW RTU SYSTEMS IN ACCORDANCE WITH ASHRAE STANDARD 183
 OR ACCA MANUAL N- SEE SECTION C403.2.1 FBC EC.
  
 2) SHEET M1: CORRECT KEY NOTE 1. THE TESTING AND
 BALANCING OF THE SYSTEMS SHALL BE PERFORMED BY A FL.
 LICENSED ENGINEER, OR A COMPANY OR INDIVIDUAL HOLDING A
 CURRENT CERTIFICATION FROM A RECOGNIZED TESTING AND
 BALANCING AGENCY ORGANIZATION IN ACCORDANCE WITH
 GENERALLY ACCEPTED ENGINEERING STANDARDS- SECTION
 C408.2.2 FBC EC.
  
 3) M1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY
 AIR SYSTEM OF THE NEW 5-TON RTU-4 SYSTEM PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S PERFORMANCE DATA TABLES INDICATE
 THE AIR HANDLER IS NOT CAPABLE OF PRODUCING OVER 2000
 CFMS OF SUPPLY AIR.
  
 4) M1, AC EQUIPMENT SCHEDULE:
  
 A) MANUFACTURER OF THE SYSTEMS MISSING- SECTION 107.2.1
 WPB.
  
 B) EFFICIENCY RATINGS MISSING- TABLE C403.2.3(1) FBC EC
  
 C) INCORRECT COOLING MBH VALUES LISTED- SECTION 107.2.1
 WPB
  
 D) NO INDICATION OF HOW O/A WILL BE PROVIDED AND
 AUTOMATICALLY CONTROLLED- SECTION C403.2.4.3 FBC EC.
  
 4) THE SUBMITTED CUT SHEETS FOR THE GAS FIRED COOKING
 APPLIANCES DO NOT INDICATE THE APPLIANCES HAVE BEEN
 TESTED IN ACCORDANCE WITH EITHER ANSI Z21.1, ANSI
 Z21.58, OR ANSI Z83.11 AS REQUIRED PER SECTION 623.1
 FBC FG.
  
 5) M1: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO
 THE COOKING APPLIANCES AND PROVIDE CALCULATIONS- SEE
 SECTION 304 FBC FG.
  
 6) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOOD, FIRE SUPPRESSION SYSTEM, AND
 WALKIN COOLERS AND FREEZERS. PLEASE PROVIDE A COST
 BREAKDOWN FOR THE ENTIRE PROJECT THAT SHOWS THE COSTS
 OF THESE ITEMS REMOVED FOM THE TOTAL VALUE OF THE
 PROPOSED RESTAURANT- SECTIONS 107.2.1 & 109.3 WPB.
  
 7) ADVISORY: CONCERNING THE KITCHEN HOOD SYSTEM, IT IS
 IMPORTANT TO NOTE THE MAKEUP AIR TEMPERATURE
 REQUIREMENT UNDER SECTION 508.1.1 FBC M BECAUSE IT MAY
 IMPACT THE MAIN RESTAURANT PLANS. 508.1.1 MAKEUP AIR
 TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  