| 2020-02-05 09:43:29 | 1ST REVIEW: 20010651 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. PLEASE CLARIFY THE NUMBER OF TANKLESS HEATERS SHOW |
| | THEM ON THE GAS ANS WATER ISOMETRIC PROVIDE A PIPING |
| | DETAIL FOR THE TANKLESS WATER HEATERS. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 2. SHT. P3 THE NOTE NEXT TO WATER HEATER SCHEDULE SHALL |
| | STATE THE INSULATION ON THE HOT WATER PIPING SHALL BE A |
| | MIN OF 1". PER FBC PL 607.5 AND FBC ENG TABLE C403.2.10 |
| | |
| | 3. THE SEDIMENT TRAPS SHOWN ON THE ISOMETRIC ARE NOT |
| | CODE COMPLIANT THE CAN NOT BE PLACED IN THE RUN OF THE |
| | PIPE THEY SHALL BE INSTALLED WITH THE CAP AT THE BOTTOM |
| | OF THE TEE WHERE THE PIPING IS GOING FROM HORIZONTAL TO |
| | VERTICAL SHALL COMPLY WITH FBC FG 408.4 |
| | |
| | 4. PLEASE PROVIDE THE SIZING TABLE FOR THE .5LB PIPING |
| | BETWEEN THE REGULATOR AND THE GAS APPLIANCES AND |
| | INCLUDE DISTANCE. PER FBC FG 402.4 |
| | |
| | 5. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION |
| | GUIDES FOR THE REGULATORS AND TANKLESS WATER HEATERS |
| | WHAT WAS PROVIDED ON THE PLAN IS NOT SUFFICIENT THEY |
| | SHALL SHOW APPROVAL FOR OUTDOOR USE. |
| | |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2017 FUEL GAS CODE SEC. 304. |
| | |
| | 7. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH, |
| | SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL |
| | GAS CODE SEC. 502 THRU 505. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |