| Date |
Text |
| 2020-01-21 16:12:20 | 01/21/20 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. WATER HEATER EF 0.92 ON A 50 GALLON ON FORM |
| | R405-2017 IS NOT CORRECT ACCORDING TO NEACA HOT WATER |
| | REGULATION 2015 AND IT SHOULD BE AT EF 0.95, PLEASE |
| | VISIT HTTP://WWW.CASHACME.COM/RESOURCES/NAECA-2015-REGU |
| | LATIONS/ FOR FURTHER DETAILS. |
| | 2. WATER HEATER IS OUTSIDE, AND IT DOES NOT HAVE ANY |
| | PROTECTION FROM THE OUTSIDE ELEMENTS. IF YOU ARE GOING |
| | TO KEEP IT OUTSIDE A STRUCTURE NEEDS TO BE SUBMITTED |
| | AND REVIEWED BY THE BUILDING PLAN EXAMINER AND APPROVE |
| | OTHER WISE BRING THE UNIT INSIDE PER THE MANUFACTURE |
| | SPECIFICATION AND WARRANTIES. |
| | 3. A REDUCED PRESSURE ZONE (RPZ) BACKFLOW PREVENTER |
| | WILL BE REQUIRED SINCE THIS A DUAL DWELLING PER THE |
| | CITY OF WEST PALM BEACH ORD #2853-95 AND IN THEIR |
| | CROSS-CONNECTION MANUAL. A PERMIT REQUIRED BY A |
| | LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| | PRIOR TO FINAL INSPECTION. PLEASE CONTACT THE CITY OF |
| | WPB UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS. |
| | 4. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM |
| | [email protected] |
| | 561-701-6437 |
| | |