| Plan Review Notes For Permit 20010495 |
| Permit Number |
20010495 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-05 09:45:10 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | 1. FBC R M 1401.1, 1401.2, 1401.3, PROVIDE THE | | | MANUFACTURERS SPECIFICATIONS INCLUDING THE CFM | | | CAPACITY. | | | 2. FBC R M 1411.3 PROVIDE DETAILS INCLUDING LOCATION OF | | | CONDENSATE DISPOSAL DETAILS. | | | 3. FBC R M 1401.4/1401.5 PROVIDE THE MANUFACTURER'S | | | SPECIFICATIONS FOR EXTERIOR CONDENSING UNIT ANCHORING | | | DETAILS. | | | |
|