| 2020-02-15 09:05:29 | PLAN REVIEW - MECHANICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. MECHANICAL SUB-PERMIT REQUIRED |
| | 105.1 REQUIRED. |
| | |
| | 2. PROVIDE ENERGY GUAGE FORM 405 AND MANUAL J |
| | WORKSHEETS. |
| | 1) ENERGY GAUGE FORM R405 - SECTION R405.2 FBC EC. |
| | |
| | 2) PROVIDE MANUAL J WORKSHEETS - AC SYSTEM SIZING |
| | CALC?S - SECTION R403.7.1 FBC EC. |
| | |
| | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| | (MANDATORY). |
| | |
| | 3. MECHANICAL CONTRACTOR OR DESIGNER OF RECORD SHALL |
| | SIGN PLAN. |
| | TITLE BLOCK AND SIGNATURE OF DESIGNER |
| | THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A |
| | TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET |
| | M-1 |
| | SECTION 107.2.1 WPB. |
| | |
| | 4. PROVIDE TAMPER PROOF LOCKING GAS CAPS |
| | M1411.8 LOCKING ACCESS PORT CAPS. |
| | REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL |
| | BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR |
| | SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED |
| | ACCESS. |
| | EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE |
| | REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING |
| | UNIT CABINET. |
| | |
| | 5. CONDENSING UNIT MOUNTING DETAIL |
| | M -1: PROVIDE ENGINEERING FOR INSTALLATION OF THE |
| | CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS |
| | M1305.1.4.1 AND M1401.4 FBC RES. |
| | |
| | 6. SHOW LOCATION OF BATHROOM EXHAUST FANS AND DISCHARGE |
| | ON PLAN |
| | NOTES 1 AND 4 ON MECH. PLAN DO NOT SPECIFY THEIR |
| | INTENDED USE |
| | M1501.1OUTDOOR DISCHARGE. |
| | THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM |
| | SHALL BE DISCHARGED TO THE OUTDOORS IN ACCORDANCE WITH |
| | SECTION M1506.3. AIR SHALL NOT BE EXHAUSTED INTO AN |
| | ATTIC, SOFFIT, RIDGE VENT OR CRAWL SPACE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |