| 2020-02-15 10:00:55 | PLAN REVIEW - ELECTRICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. ELECTRICAL SUB-PERMIT REQUIRED |
| | PERMITS - 105.1 REQUIRED. |
| | |
| | 2. TITLE BLOCK AND SIGNATURE OF DESIGNER |
| | THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A |
| | TITLE BLOCK AND SIGNATURE ON THE ELECTRICAL PLAN SHEET |
| | E-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL. |
| | LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO |
| | PROVIDE AN ORIGINAL SEAL AND SIGNATURE PER FL. STATUE |
| | AND SECTIONS 61G15-16.003 AND 23.002 FAC. |
| | |
| | 3. AIC: |
| | PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM |
| | UTILITY. |
| | |
| | E3404.2INTERRUPTING RATING. |
| | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS |
| | SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 |
| | AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| | LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT |
| | LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) |
| | |
| | PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC |
| | 110.3, 110.9; FBC RE E3606.4 |
| | |
| | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED |
| | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24 & FBC RE E3606.4 |
| | |
| | 4. REMOVE REFERENCE ON PANEL SCHEDULE TO SMALL |
| | APPLIANCES FROM MASTER BATH CIRCUT #22 AND BATH #1 |
| | CIRCUT #24. |
| | A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |