| 2020-02-15 07:54:00 | PLAN REVIEW - BUILDING |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. CITY OF WPB CHPT. 1 ? VALUE |
| | 109.3 BUILDING PERMIT VALUATIONS. |
| | VALUATION ? BASED ON THE INTERNATIONAL CODE COUNCIL |
| | (ICC) BUILDING VALUATION DATA YOUR STATED VALUE HAS |
| | BEEN CHANGED FROM $80,000 TO $185,770. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2. PROVIDE SURVEY AND SITE DRAINAGE PLAN |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| | AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED ON A BOUNDARY LINE SURVEY. |
| | |
| | 3. PROVIDE FINISHED FLOOR ELEVATION |
| | R403.1.7.3 FOUNDATION ELEVATION. |
| | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO |
| | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN |
| | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| | ALL LOCATIONS ON THE SITE. |
| | |
| | 4. ROOFING, MECHANICAL, ELECTRICAL & PLUMBING |
| | SUB-PERMITS REQUIRED - |
| | PERMITS 105.1 REQUIRED. |
| | |
| | 5. PROVIDE PRODUCT APPROVALS |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR |
| | SUBMITTALS. |
| | |
| | 6. PROVIDE ENERGY SUBMITTAL AND EPL DISPLAY CARD |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.+ |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | 1) ENERGY GAUGE FORM R405 - SECTION R405.2 FBC EC. |
| | |
| | 2) PROVIDE MANUAL J WORKSHEETS - AC SYSTEM SIZING |
| | CALC?S - SECTION R403.7.1 FBC EC. |
| | |
| | 3) R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| | (MANDATORY). |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |