| Plan Review Notes For Permit 20010487 |
| Permit Number |
20010487 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-21 16:06:25 | ****CORRECTIONS**** (REVISED 2/10, REMOVED #2) | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC A 404.2.6, A1.1.1, DOORS IN A SERIES, REVISE | | | PLAN TO SHOW THE 4' REQUIRED BETWEEN THE DOORS 105 AND | | | 100, VESTIBULE AT ACCESSIBLE BATHROOMS. | | | | | | |
|