| Plan Review Notes For Permit 20010400 |
| Permit Number |
20010400 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-03 06:42:12 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | 1. FBC B 107.2.1, THE NOTES FOUND ON PAGES M01 AND M02 | | | STATE THAT THE HVAC SYSTEM SHALL COMPLY WITH FBC EC 5TH | | | EDITION ENERGY. THIS NEEDS TO BE CORRECTED TO THE FBC | | | EC 6TH EDITION. | | | 2. FBC M 504.10 (11), THE DRYER EXHAUST DUCT NOTE | | | INDICATES AN EXHAUST CAP WITH GRAVITY DAMPER AND INSECT | | | SCREEN. ITEM #11 OF FBC M 504.10 STATES THAT SCREENS | | | SHALL NOT BE INSTALLED AT THE TERMINATION. ALSO PLEASE | | | SHOW LOCATION OF THE DRYER EXHAUST TERMINATION AT THE | | | UTILITY ROOM. | | | 3. FBC M 307.1, THE PLANS NEED TO INDICATE THE LOCATION | | | OF CONDENSATE LINES AND TERMINATION. | | | 4. FBC M 301.15, PROVIDE ENGINEERING FOR | | | TIE-DOWNS/CONNECTIONS OF THE EXTERIOR CONDENSATE LINES. | | | 5. FBC B 107.2.1 THE CONDENSING UNIT FOR A/C #1 IS A 15 | | | SEER, THIS DOES NOT MEET THE ARCHITECT'S REQUIREMENT | | | FOUND ON PAGE A-00 UNDER ENERGY CODE COMPLIANCE NOTE | | | #14 WHICH CALLS FOR ALL A/C EQUIPMENT TO MEET A MINIMUM | | | OF 16 SEER. |
|