2020-02-03 06:42:12***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW DENIED:
  
 1. FBC B 107.2.1, THE NOTES FOUND ON PAGES M01 AND M02
 STATE THAT THE HVAC SYSTEM SHALL COMPLY WITH FBC EC 5TH
 EDITION ENERGY. THIS NEEDS TO BE CORRECTED TO THE FBC
 EC 6TH EDITION.
 2. FBC M 504.10 (11), THE DRYER EXHAUST DUCT NOTE
 INDICATES AN EXHAUST CAP WITH GRAVITY DAMPER AND INSECT
 SCREEN. ITEM #11 OF FBC M 504.10 STATES THAT SCREENS
 SHALL NOT BE INSTALLED AT THE TERMINATION. ALSO PLEASE
 SHOW LOCATION OF THE DRYER EXHAUST TERMINATION AT THE
 UTILITY ROOM.
 3. FBC M 307.1, THE PLANS NEED TO INDICATE THE LOCATION
 OF CONDENSATE LINES AND TERMINATION.
 4. FBC M 301.15, PROVIDE ENGINEERING FOR
 TIE-DOWNS/CONNECTIONS OF THE EXTERIOR CONDENSATE LINES.
 5. FBC B 107.2.1 THE CONDENSING UNIT FOR A/C #1 IS A 15
 SEER, THIS DOES NOT MEET THE ARCHITECT'S REQUIREMENT
 FOUND ON PAGE A-00 UNDER ENERGY CODE COMPLIANCE NOTE
 #14 WHICH CALLS FOR ALL A/C EQUIPMENT TO MEET A MINIMUM
 OF 16 SEER.