2020-02-06 15:42:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 2. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9; FBC RE E3606.3
 3. FEED FROM ATS TO MAIN PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE.
 ADDITIONALLY, AND SUB-PANEL FED FROM A PANEL AFTER THE
 FIRST MEANS OF DISCONNECT IS REQUIRED TO HAVE THE EGC.
 PROVIDE CORRECTION FOR ALL FEEDERS. NEC 250.122; FBC RE
 E3704.6, 3607.3.1
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. LOAD CALCULATIONS ARE SHOWN FOR
 INDIVIDUAL PANELS, BUT NOT FOR THE SERVICE. NEC 215.2,
 220, 408.30; FBC RE E3602.2
 5. ELECTRICAL PLAN SHOWS A 200 AMP SERVICE WITH A 200
 AMP TRANSFER SWITCH. RISER DIAGRAM SHOWS A 400 AMP
 SERVICE WITH A 400 AMP TRANSFER SWITCH. CORRECT
 DISCREPANCY. WPB FBC 107.2.1
 6. RISER DIAGRAM SHOWS A 2/0 FEEDER FOR A 200 AMP
 PANEL. THIS WIRE IS NOT SIZED PROPERLY. WIRE SIZES FROM
 NEC 310.15(B)(7), OR FBC RE E3603.1, CAN ONLY BE USED
 WHEN THE SERVICE CONDUCTOR SUPPLIES 100% OF THE LOAD.
 SINCE THIS IS NOT THE CASE, PROVIDE CORRECTED WIRE SIZE
 FOR THIS FEEDER. NEC 310.15(B)(7) AND (B)(16); FBC RE
 E3603.1, E3705.1
 7. RISER DIAGRAM SHOWS A #4 FEEDER FOR A 100 AMP PANEL
 IN TWO LOCATIONS. THIS WIRE IS NOT SIZED PROPERLY. WIRE
 SIZES FROM NEC 310.15(B)(7), OR FBC RE E3603.1, CAN
 ONLY BE USED WHEN THE SERVICE CONDUCTOR SUPPLIES 100%
 OF THE LOAD. SINCE THIS IS NOT THE CASE, PROVIDE
 CORRECTED WIRE SIZE FOR THIS FEEDER. NEC 310.15(B)(7)
 AND (B)(16); FBC RE E3603.1, E3705.1
 8. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 9. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D); FBC RE E3902.10
 10. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 11. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 680.21(C); FBC RE
 E4203.1.3
 12. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 13. LIGHTING IN CLOSETS IS SHOWN AS A J-BOX FOR A
 CELING MOUNTED OR HANGING DECORATIVE FIXTURE. PER CODE,
 LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE A BLOCK NOTE THAT
 COMPLIANCE IS REQUIRED. NEC 410.16; FBC RE E4003.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER