Plan Review Notes
Plan Review Notes For Permit 20010398
Permit Number 20010398
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-07 08:28:02BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 20010398
 REVIEWED: FEBRUARY 7, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FAIRHOUSING ACT (MULTIFAMILY DWELLINGS BUILT AFTER
 MARCH 13, 1991)
  
 1) 109.3 FBC[AMENDED]PLEASE PROVIDE COPY OF PROPOSAL
 WITH CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT
 SHOWN ON PERMIT APPLICATION.
  
 2) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 501 FBC[EXISTING]IF WORK AREA COMPLIANCE PLEASE STATE
 THE LEVEL OF ALTERATION FOR WORK BEING PERFORMED.
 A) LEVEL 1 ALTERARTION
 B) LEVEL 2 ALTERARTION
 C) LEVEL 3 ALTERARTION
 - PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA.
 -ADD NOTE THAT FLOORING IS UNDER SEPARATE PERMIT
  
 3) THIS BUILDING WOULD HAVE BEEN BUILT WITH FAIRHOUSING
 ACT STANDARDS.
 PLEASE ADD TO COVER SHEET WHICH SAFE HARBOR STANDARD IS
 USED FOR FAIRHOUSING.
  
 101.4.1 FBC[EXISTING]BUILDINGS NOT PREVIOUSLY OCCUPIED.
 A BUILDING OR PORTION OF A BUILDING THAT HAS NOT BEEN
 PREVIOUSLY OCCUPIED OR USED FOR ITS INTENDED PURPOSE IN
 ACCORDANCE WITH THE LAWS IN EXISTENCE AT THE TIME OF
 ITS COMPLETION SHALL BE PERMITTED TO COMPLY WITH THE
 PROVISIONS OF THE LAWS IN EXISTENCE AT THE TIME OF ITS
 ORIGINAL PERMIT UNLESS SUCH PERMIT HAS EXPIRED.
 SUBSEQUENT PERMITS SHALL COMPLY WITH THE FLORIDA
 BUILDING CODE, BUILDING OR FLORIDA BUILDING CODE,
 RESIDENTIAL, AS APPLICABLE, FOR NEW CONSTRUCTION.
  
 IN LOOKING AT UNDIMENSIONED PLANS IT APPEARS THAT CLEAR
 SPACE WILL BE PROVIDED.
 HOWEVER, PLEASE INDICATE WHAT UNITS ARE APPLICABLE TO
 FAIRHOUSING STANDARDS.
 ARE THERE ELEVATORS TO EACH FLOOR? IF YES THAN
 FAIRHOUSING APPLIES TO ALL UNITS.
 FOR THE UNITS WHERE FAIRHOUSING APPLIES INDICATE WHAT
 SPECIFICATION THE BATH IS, SHOW CLEAR FLOOR SAPCE AT
 KITCHEN AND BATHROOM FIXTURES.
  
 REQUIREMENT 7 - USABLE BATHROOMS.
 VERIFY THE NEW VANITY MEETS HEIGHT REQUIREMENTS. ADD
 DETAIL OF CABINET TO SHOW COMPLIANCE.
  
 4) R-2 UNITS ARE SUBJECT TO FIRE RATINGS AND IT SHOWS
 THAT PLUMBING AND ELECTRICAL IS BEING ALTERED IN THE
 KITCHEN SOFFITS.
 PLEASE STATE WHAT RATING IS REQUIRED AT CEILING AND
 PROVIDE TESTED ASSEMBLY THAT WILL BE USED TO MAINTAIN
 THAT RATING.
  
 420.3 FBC[B]HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 711.2.4.3 FBC[B]DWELLING UNITS AND SLEEPING UNITS.
 HORIZONTAL ASSEMBLIES SERVING AS DWELLING OR SLEEPING
 UNIT SEPARATIONS IN ACCORDANCE WITH SECTION 420.3 SHALL
 BE NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED
 CONSTRUCTION. EXCEPTION: HORIZONTAL ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS SHALL BE
 NOT LESS THAN 1/2- HOUR FIRE-RESISTANCE-RATED
 CONSTRUCTION IN A BUILDING OF TYPE IIB, IIIB AND VB
 CONSTRUCTION, WHERE THE BUILDING IS EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1.
  
 5) 711.2.4.3 FBC[B]PLEASE ADD NOTE ON COVER IF THE
 UNITS ARE SPRINKLED AND THE TYPE OF CONSTRUCTION AS
 WELL.
  
 6) 714 FBC[B]IF PENETRATIONS ARE ALTERED OR CREATED
 PLEASE PROVIDE TESTED ASSEMBLIES THAT SHOW COMPLIANCE
 WITH SECTION 714 PENETRATIONS.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
2020-01-15 11:02:30PLEASE SEE COST BREAKDOWN DOCUMENT AND COORDINATE WITH
 SAK. SEE ATTACHMENT. LEM