Plan Review Notes
Plan Review Notes For Permit 20010346
Permit Number 20010346
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-15 05:47:411) THE DOCUMENTS THAT HAVE BEEN SUBMITTED ARE NOT THE
 MANUFACTURER'S SPECIFICATIONS AND DO NOT SHOW THE
 DEVICE IS LEAD FREE. THE ZURN 975 XL IS NOT A LEAD FREE
 DEVICE AND CANNOT BE INSTALLED.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS THAT SHOW THE DEVICE IS LEAD FREE AND IS
 ON THE UNIVERSITY OF SOUTHERN CALIFORNIA'S LIST OF
 APPROVED DEVICES. PER THE CITY OF WEST PALM BEACH CROSS
 CONNECTION CONTROL MANUAL AS ADOPTED BY ORDINANCE.
 3) THIS WORK MUST BE DONE BY A LICENSED PLUMBING
 CONTRACTOR PER FL. STATUTE 489.105. SUBMIT AN
 APPLICATION FROM A LICENSED PLUMBING CONTRACTOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW