| 2020-01-30 06:47:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 |
| | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. |
| | FBC-EC 405.2.5. PROVIDE CORRECTION. |
| | |
| | 2. PROVIDE ELECTRICAL DRAWING SHOWING CONDUIT, WIRE |
| | SIZE, CIRCUIT NUMBER AND PANEL WHERE CIRCUIT IS FED |
| | FROM. FBC 107.2.1 |
| | |
| | 3. THE VALUE FOR SITE LIGHTING IS NOT TO BE INCLUDED IN |
| | THE MAIN PERMIT REVIEW. PLEASE CONTACT SAMANTHA HILL |
| | (CHIEF PLANS EXAMINER) @ [email protected] WITH A COPY OF |
| | THE ELECTRICIAN'S CONTRACT AND THE GENERAL CONTRACTOR'S |
| | CONTRACT TO VERIFY THE PROPER FEES HAVE BEEN COLLECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |