| Plan Review Notes For Permit 20010338 |
| Permit Number |
20010338 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-13 08:31:22 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) FIXTURE LISTING REQUIRED THEY DON'T LOOK TO BE | | | LISTED FOR OUTDOORS USE. (INCLUDING THE WALL SCONCE) | | | 110.3 | | | | | | 2) NEED BRANCH CIRCUIT NUMBERS AND A DIAGRAM SHOWING | | | THE LOCATION OF THE FIXTURES AND OUTLETS AND SIZES | | | 210.5, 215.5 | | | | | | 3) EXIT AND EMERGENCY LIGHTS??????? |
|