Plan Review Notes
Plan Review Notes For Permit 20010335
Permit Number 20010335
Review Stop P
Sequence Number 2
Notes
Date Text
2020-02-19 16:03:122ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1) A HOT WATER RECIRCULATION LINE IS REQUIRED PER 2017
 FBC-PLUMBING SEC.607.2.
 2) SHOW THE RECIRCULATION LINE ON THE WATER RISER. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) THE RECIRCULATION PUMP DOES NOT COMPLY WITH FBC PL
 607.2.1.2 ON A SYSTEM THAT USE THE COLD WATER PIPING TO
 RETURN BACK TO THE WATER HEATER SHALL HAVE A SENSOR
 THAT STARTS THE PUMP.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  