| 2020-01-15 11:10:10 | 1) SUBMIT AN ENLARGED FLOOR PLAN FOR TOILET ROOM #515 |
| | (CEO) AND TOILET ROOM # 518. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 2) THE WALL NEXT TO THE WATER CLOSET IN TOILET ROOM # |
| | 515 DOE NOT APPEAR TO BE LONG ENOUGH TO ACCEPT A 42 |
| | INCH GRAB BAR. CLARIFY. |
| | 3) IF THE SHOWER IN ROOM #515 IS A STANDARD ROLL IN |
| | SHOWER, A 30 INCH WIDE MINIMUM BY 60 INCH LONG MINIMUM |
| | CLEAR FLOOR SPACE SHALL BE PROVIDED ADJACENT TO THE |
| | OPEN FACE OF THE SHOWER COMPARTMENT PER 2017 |
| | FBC-ACCESS. SEC.608.2.2.1. CLARIFY. |
| | 4) THE INSTALLATION OF THE GRAB BARS SHALL COMPLY WITH |
| | 2017 FBC-ACCESS. SECS.604.5. SHOW COMPLIANCE ON |
| | SHT.A-9.. |
| | 5) THE MIRRORS IN THE ACCESSIBLE TOILET ROOMS SHALL |
| | COMPLY WITH 2017 FBC-ACCESS. SEC.603.3 |
| | 6) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET IN |
| | TOILET ROOM #515. COMPLY WITH 2017 FBC-ACCESS. |
| | SEC.604.3.1. |
| | 7) THE TOILET PAPER DISPENSER SHALL COMPLY WITH 2017 |
| | FBC-ACCESS. SEC.604.7. |
| | 8) TOILET ROOM #515 SHOWS THE DOOR OF THE CLOSET |
| | SWINGING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY. |
| | COMPLY WITH 2017 FBC-ACCESS. SEC.603.2.3. |
| | 9) THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW |
| | PREVENTER ON THE WATER LINE PER 2017 FBC-PLUMBING |
| | SEC.608.2. |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE |
| | BLODGETT OVEN.WPB AMEND. TO FBC SE. 107.1. |
| | 11) A HOT WATER RECIRCULATION LINE IS REQUIRED PER 2017 |
| | FBC-PLUMBING SEC.607.2. |
| | 12) SHOW THE RECIRCULATION LINE ON THE WATER RISER. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |