Plan Review Notes
Plan Review Notes For Permit 20010335
Permit Number 20010335
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-01-15 14:59:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THERE IS NO INDICATION OF COMPLIANCE
 WITH THE FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 2) SHEET A 1 - THERE ARE PLAN SHEET INDICATORS OF FP 1,
 FA 1 & FA 2; HOWEVER, THERE ARE NO CORRESPONDING PLAN
 SHEET ATTACHED.
  
 PLEASE REVIEW AND CORRECT
  
  
 3) ALL SHEETS - THERE IS NO SUITE NUMBER INDICATED ON
 ANY PLAN SHEET.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 4) SHEET A 6 - THERE IS NO INDICATION OF EXISTING LIFE
 SAFETY SYSTEMS; FIRE SPRINKLER & FIRE ALARM.
  
 EXISITNG LIFE SAFETY SYSTEMS SHALL REMIAN FUNCTIONAL
 AND ACTIVE THROUGHOUT DEMO AND CONSTRUCTION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  