| Date |
Text |
| 2020-03-24 14:07:52 | 20010288 901 45TH ST |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: APPROVED W/PROVISO |
| | 1. PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT |
| | LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE |
| | PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE AND SHALL |
| | COMPLY WITH FBC ACC 606 WHICH REQUIRES ACCESSIBLE SINKS |
| | TO HAVE A CLEAR FLOOR SPACE COMPLYING WITH 305, |
| | POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED (606.2) |
| | AS WELL AS SAID SINK SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND |
| | (606.3). PER WPB FBC 107.2.1, PROVIDE PLAN REVISION |
| | PROVIDING FOR THE SAME OR PROVIDE AN AFFIDAVIT STATING |
| | THAT A STAFF MEMBER WHO WOULD USE THE FACILITY IS |
| | DISABLED THAT THE FACILITY WILL MAKE THE REQUIRED |
| | CHANGES TO ACCOMMODATE SAID STAFF MEMBER. SAID |
| | AFFIDAVIT SHALL BE SUBMITTED AND IN PLACE PRIOR TO |
| | FIRST INSPECTION. A PLAN REVISION IF REQUIRED, SHALL BE |
| | IN PLACE PRIOR TO FINAL INSPECTION. |
| | 2. REGARDING RO SYSTEM BY OWNER: |
| | 1) A SEPARATE PERMIT IS REQUIRED. |
| | 2) PER FBC PL 608.3, PROVIDE A BACKFLOW PREVENTOR13.1 |
| | AT THE COLD WATER SUPPLY FOR THE RO SYSTEM. |
| | 3) PROVIDE A TRAPPED AND VENTED DRAIN WITH OPEN |
| | RECEPTACLE FOR THE RO DRAIN. RO DRAIN AND BACKFLOW |
| | PREVENTOR VENT DRAIN SHALL DISCHARGE INTO THE OPEN |
| | RECEPTACLE THROUGH AN AIR GAP IN ACCORDANCE WITH FBC PL |
| | 608.13.1. |
| | |
| | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| | INSPECTOR'S APPROVAL |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 20010288 901 45TH ST |
| | |
| | |
| | |