Plan Review Notes
Plan Review Notes For Permit 20010288
Permit Number 20010288
Review Stop P
Sequence Number 2
Notes
Date Text
2020-03-24 14:07:5220010288 901 45TH ST
  
 1ST REVIEW
 PLUMBING COMMENTS: APPROVED W/PROVISO
 1. PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE
 PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE AND SHALL
 COMPLY WITH FBC ACC 606 WHICH REQUIRES ACCESSIBLE SINKS
 TO HAVE A CLEAR FLOOR SPACE COMPLYING WITH 305,
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED (606.2)
 AS WELL AS SAID SINK SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 (606.3). PER WPB FBC 107.2.1, PROVIDE PLAN REVISION
 PROVIDING FOR THE SAME OR PROVIDE AN AFFIDAVIT STATING
 THAT A STAFF MEMBER WHO WOULD USE THE FACILITY IS
 DISABLED THAT THE FACILITY WILL MAKE THE REQUIRED
 CHANGES TO ACCOMMODATE SAID STAFF MEMBER. SAID
 AFFIDAVIT SHALL BE SUBMITTED AND IN PLACE PRIOR TO
 FIRST INSPECTION. A PLAN REVISION IF REQUIRED, SHALL BE
 IN PLACE PRIOR TO FINAL INSPECTION.
 2. REGARDING RO SYSTEM BY OWNER:
 1) A SEPARATE PERMIT IS REQUIRED.
 2) PER FBC PL 608.3, PROVIDE A BACKFLOW PREVENTOR13.1
 AT THE COLD WATER SUPPLY FOR THE RO SYSTEM.
 3) PROVIDE A TRAPPED AND VENTED DRAIN WITH OPEN
 RECEPTACLE FOR THE RO DRAIN. RO DRAIN AND BACKFLOW
 PREVENTOR VENT DRAIN SHALL DISCHARGE INTO THE OPEN
 RECEPTACLE THROUGH AN AIR GAP IN ACCORDANCE WITH FBC PL
 608.13.1.
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20010288 901 45TH ST
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved