2020-01-14 14:40:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A 125 AMP PANEL BEING FED WITH #
 3 WIRE. THIS WIRE IS NOT RATED FOR 125 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16); FBC RE E3705.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. LOAD CALCULATION PROVIDED IS ONLY
 FOR SUB-PANEL. THIS IS NEEDED IN ADDITION TO THE LOAD
 FOR THE WHOLE SERVICE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 3. RISER SHOWS NEW SERVICE BEING INSTALLED DUE TO
 RELOCATION. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION
 FOR SERVICE INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9,
 110.10; FBC RE E3606.3
 4. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9; FBC RE E3606.3
 5. RISER SHOWS A 125 AMP FEED TO SUB-PANEL. THIS FEED
 DOES NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR.
 PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6,
 3607.3.1
 6. IF THE INTENTION OF THIS REVISION IS TO INSTALL A
 SEPARATE SERVICE TO THIS STRUCTURE, THAT IS NOT
 PERMITTED PER CODE. ONLY ONE SERVICE IS PERMITTED,
 UNLESS ONE OF THE EXCEPTIONS IS MET. BE ADVISED THAT A
 SEPARATE METER IS POSSIBLE IF ZONING APPROVES, BUT NOT
 A SEPARATE SERVICE LOCATION. MAINS MUST BE GROUPED.
 PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 230.2; FBC
 RE E3601.2
 7. IF THE INTENT IS TO RELOCATE THE SERVICE TO THIS
 STRUCTURE AND RE-FEED THE MAIN HOUSE, THIS SHOULD BE
 SHOWN ON PLAN. PROVIDE CLARIFICATION AND/OR
 CORRECTIONS. NEC 215.5; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER