| 2020-01-14 14:40:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM SHOWS A 125 AMP PANEL BEING FED WITH # |
| | 3 WIRE. THIS WIRE IS NOT RATED FOR 125 AMPS. PROVIDE |
| | CORRECTION. NEC 310.15(B)(16); FBC RE E3705.1 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. LOAD CALCULATION PROVIDED IS ONLY |
| | FOR SUB-PANEL. THIS IS NEEDED IN ADDITION TO THE LOAD |
| | FOR THE WHOLE SERVICE. NEC 215.2, 220, 408.30; FBC RE |
| | E3602.2 |
| | 3. RISER SHOWS NEW SERVICE BEING INSTALLED DUE TO |
| | RELOCATION. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION |
| | FOR SERVICE INCLUDING INFORMATION FROM THE POWER |
| | COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| | CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC |
| | RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, |
| | 110.10; FBC RE E3606.3 |
| | 4. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9; FBC RE E3606.3 |
| | 5. RISER SHOWS A 125 AMP FEED TO SUB-PANEL. THIS FEED |
| | DOES NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. |
| | PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6, |
| | 3607.3.1 |
| | 6. IF THE INTENTION OF THIS REVISION IS TO INSTALL A |
| | SEPARATE SERVICE TO THIS STRUCTURE, THAT IS NOT |
| | PERMITTED PER CODE. ONLY ONE SERVICE IS PERMITTED, |
| | UNLESS ONE OF THE EXCEPTIONS IS MET. BE ADVISED THAT A |
| | SEPARATE METER IS POSSIBLE IF ZONING APPROVES, BUT NOT |
| | A SEPARATE SERVICE LOCATION. MAINS MUST BE GROUPED. |
| | PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 230.2; FBC |
| | RE E3601.2 |
| | 7. IF THE INTENT IS TO RELOCATE THE SERVICE TO THIS |
| | STRUCTURE AND RE-FEED THE MAIN HOUSE, THIS SHOULD BE |
| | SHOWN ON PLAN. PROVIDE CLARIFICATION AND/OR |
| | CORRECTIONS. NEC 215.5; WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |