Plan Review Notes
Plan Review Notes For Permit 20010166
Permit Number 20010166
Review Stop P
Sequence Number 3
Notes
Date Text
2021-02-04 08:49:4802/04/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 THIS IS A SECOND REQUEST FOR THE INFORMATION BELOW.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE PROVIDE A DESCRIPTIVE SCOPE OF WORK BEING
 DONE PER THE 2017 FBC WPB AMENDMENTS SEC. 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 3. PLUMBING RISER DIAGRAM FOR THE SANITARY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING.
  
 4. HOT WATER AND COLD NOT SHOW AND ITS SOURCE, SIZING,
 DISTRIBUTION, SHUTOFF VALVES, WATER HAMMER, WITHIN
 ACCORDANCE 2017 FBC P SEC. 604, PLEASE PROVIDE A LAYOUT
 AND RISER WPB AMENDMENTS TO THE FBC 107.5.1.3 (13)
 PLUMBING RISER DIAGRAM REQUIRED.
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
  
 6. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 7. PLEASE SUBMIT A SLAB REPAIR DETAIL AND SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE DOWELS' SIZE AND LENGTH, THE MINIMUM EMBEDMENT
 DEPTH INTO THE EXISTING SLAB, AND THE SPACING OF THE
 DOWELS IN THE CENTER. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR
 BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 8. ALL PLUMBING MUST COMPLY WITH THE FLORIDA BUILDING
 CODE 2017 6TH EDITION.
  
 9. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017 FLORIDA
 EXISTING BUILDING CODE 301.1.
  
 10. ON SHEET E-1 AND E2, IT SHOWS A SINK BEHIND THE
 HANDICAP BATHROOM, AND ON A-1 AND A-2, NONE IS SHOWING.
 PLEASE CLARIFY PER THE 2017 FBC WPB AMENDMENTS SEC.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 11. SHEET E-2 HAS A DISHWASHER. PLEASE SHOW THE
 LOCATION AND DISCHARGE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. PLEASE SHOW THE SOURCE OF HOT WATER FOR THE HC
 RESTROOM AND KITCHEN AREA PER THE 2017 FBC WPB
 AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS.
  
 13. TOILET PAPER DISPENSER MISSING DIMENSION, THE
 TOILET PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND
 9" INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED
 TO THE CENTERLINE OS DISPENSER PER THE 2017 FBC ACC
 SEC. 604.7.
  
 14. ON SHEET A-2, ADA DETAIL OF HEIGHTS AND DIMENSIONS
 OF KITCHEN SINKS NOT SHOWN. PLEASE PROVIDE DETAILED
 DRAWINGS PER THE 2017 FBC ACCESSIBILITY. PLEASE GIVE
 MEASUREMENTS FOR FIXTURE CLEARANCES FOR SINKS PER THE
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
 PLEASE SHOW CLEAR FLOOR SPACE FOR A FORWARD OR SIDE
 APPROACH, AND IT SHALL COMPLY PER THE 2017 ACC SEC.
 602.2.
  
 15. ON SHEET A-2, PLEASE PROVIDE GRAB BARS PER THE 2017
 FBC ACC. 604.5.
  
 16. PROVIDE CABINET DETAIL SHOWING THE SINK HEIGHT OF
 34" INCHES MAXIMUM PER THE 2017 FBC ACC SEC. 606.3.
  
 17. THE CLEAR FLOOR SPACE SHALL BE 60" INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDEWALL, AND 56"
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER 2017 FBC ACC. SEC. 604.3.1, THE SINK SHALL NOT
 BE IN THAT CLEAR FLOOR SPACE PER THE 2017 FBC ACC SEC.
 604.3.2.
  
 18. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5.
  
 19. ON PLANS, THERE ARE TWO REFRIGERATOR SHOWS. IF THEY
 HAVE AN ICE MAKER, THEY SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2017 FBC SEC. 608.13.10.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved