| 2021-01-22 07:36:37 | 3RD REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20010166 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | PREVIOUS COMMENTS STILL HAVE NOT BEEN ADDRESSED. |
| | |
| | 1) PLEASE PROVIDE A MENU TO VERIFY HOW THIS RESIDENTIAL |
| | COOKING APPLIANCE IS TO BE USED. THIS WILL DETERMINE |
| | WHICH TYPE OF COMMERCIAL HOOD WILL BE NEED FOR THIS |
| | PROJECT. FBC M 507.1.2 ALLOWS DOMESTIC COOKING |
| | APPLIANCES USED FOR COMMERCIAL PURPOSES. THIS SECTION |
| | IS VERY CLEAR AS IT STATES ?SHALL BE PROVIDED WITH TYPE |
| | I OR TYPE II HOODS AS REQUIRED FOR THE TYPE OF |
| | APPLIANCES AND PROCESSES IN ACCORDANCE WITH SECTIONS |
| | 507.2 AND 507.3. THERE ARE SEVERAL CODE SECTIONS THAT |
| | WOULD COME INTO PLAY ONCE THE HOOD TYPE HAS BEEN |
| | ESTABLISHED INCLUDING CLEARANCE TO COMBUSTIBLES ( |
| | 507.2.6 ). |
| | |
| | 2) THE ROOM THAT WILL BE THE KITCHEN WAS PREVIOUSLY A |
| | LAB. THIS WOULD MAKE THE AREA A CHANGE OF USE. PLEASE |
| | PROVIDE OUTDOOR AIR CALCULATIONS FOR THIS CHANGE OF USE |
| | AND THE NEW BREAKROOM AREA. FBC M TABLE 403.3.1.1 |
| | |
| | 3) PLEASE PROVIDE DETAILS OF THE MAKE UP AIR SYSTEM FOR |
| | THIS NEW HOOD. FBC M 508 |
| | |
| | 4) PLEASE PROVIDE INFORMATION FOR THE DISHWASHER ON |
| | SHEET E-2. FBC M 507.3 |
| | |
| | 5) PLEASE PROVIDE AN AIR BALANCE PLAN FOR THIS EXHAUST |
| | SYSTEM. FBC M 508.1.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |