Plan Review Notes
Plan Review Notes For Permit 20010166
Permit Number 20010166
Review Stop B
Sequence Number 3
Notes
Date Text
2021-02-08 10:14:28PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017) EXISTING BUILDING
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOTE #9 ON SHEET A-1, STATES THAT THE SPACE HAS AN
 EXISTING APPROVED AUTOMATIC SPRINKLER SYSTEM IN PLACE
 TO REMAIN AND THE BUILDING CONSTRUCTION TYPE STATES
 THAT IT IS A TYPE 2A UNSPRINKLERED BUILDING. PLEASE
 CLARIFY. FBC AMEND. 107.2.1
  
 2) THE TRAVEL DISTANCE IN THE BREAKROOM SHOULD BE FROM
 THE HAND SINK TO THE EXIT. THIS APPEARS TO BE THE MOST
 REMOTE POINT IN THE ROOM FROM THE EXIT. FBC 1017.3
  
 3) FBC ACCESSIBILITY SECTION 404.2.4 REQUIRES 18" CLEAR
 ON THE LATCH SIDE OF A DOOR ON THE PULL SIDE. PLEASE
 SHOW THAT THE NEW 2830 DOOR IN THE BREAKROOM COMPLIES.
  
  